Configuring/address space
4.4 Parameter
Adjustable parameters
Table 4- 4
Parameter
ECC standard
(ECar Charging)
Charging outlet active
Integrated charging
cable
Cable locking
Cable locking
feedback
Contactor feedback
Maximum charging
current [A]
DI input voltage
If "SAE J1772" is selected in the hardware configuration, the parameter "Integrated charging
a)
cable" is automatically set to "Yes". Electromotive locking is not possible in this case.
Any PP resistor possibly plugged in is not evaluated! The maximum charging current is limited
here by the configuration of the module in TIA and by the "Maximum permissible charging current"
parameter or, when using the FC4100, by the "MaxCurr" parameter.
Any potential PP conductor of the charging cable must not be connected to the PP terminal, oth-
erwise an error is output.
Note that both feedbacks cannot be set to the internal module DI at the same time.
b)
Low level: 0 ..2.5 V; High level: 5.5 .. 12 V
c)
Low level: 0 ..5 V; High level: 11 .. 24 V
d)
34
Configurable parameters and their defaults
Value range
a)
IEC 61851-1
SAE J1772
Yes
No
Yes
No
No locking
External (via PII)
Pole reversal pulse
800 ms
Polarity reversal
permanent
Open collector
No feedback
b)
Internal module DI
External (via PIQ)
b)
No feedback
Internal module DI
External (via PIQ)
6 .. 80
12 V input
24 V input
Default setting
IEC 61851-1
Yes
No
Pole reversal pulse
800 ms
Internal module DI
External (via PIQ)
13
24 V input
c)
d)
Technology module TM ECC 2xPWM ST (6FE1242-6TM10-0BB1)
Configuration in RUN
No
No
No
No
No
No
No
No
Manual, 04/2018, A5E42681298B-AA

Advertisement

Table of Contents
loading

This manual is also suitable for:

6fe1242-6tm10-0bb1

Table of Contents