(*1) This message is displayed once when a total of 32 LSI carrier losses are detected. The LSI carrier loss occurs when an attempt is made to transmit data in the OFF
state of the 100M LINK LED indicator, which indicates that a "link not established yet" condition exists. The LSI carrier loss also occurs when, after the startup of
the LPU, a total of 32 send requests are issued by an FL.NET system program before the 100M LINK LED indicator comes on.
(*2) This type of error occurs due to an insufficient buffer space in a "high communication load" condition.
(*3) This message is displayed once when a total of 32 retries are made successively.
(*4) The IP address is duplicated with some other computer's. If the local computer is connected to the network after the other computer, the ERR LED indicator will be
turned on.
(*5) This message is displayed once when a total of eight such collisions are detected successively. If a total of 16 or more such collisions are detected successively, the
message will be displayed once when a total of 256 such collisions are detected.
(*6) This message is displayed once when a total of five such errors or underruns/overruns are detected successively.
(*7) This message is displayed once when a total of 10 such overruns are detected successively.