HEAVY DUTY WALL GUIDE (WGHD)
The Heavy Duty Wall Guide is designed to complement the Heavy Duty
Wall Support (See Figure 55). It is used as a lateral guide to prevent the
duct from flexing due to lateral loading . The proper location for a WGHD
is immediately below the outer closure band near the duct joint. The Heavy
Duty Wall Guide is bolted together with hardware provided to form a rigid
assembly.
NOTE: - Seal joint with S-375 sealant above and below support if exposed
to weather.
- Can be attached to combustible wall
Figure 55: - Wall Guide Heavy Duty (WGHD)
30
FULL ANGLE RING (FAR)
A Full Angle Ring is used as a guide to prevent the duct from flexing due to
lateral loading. The angle ring is split for ease of installation. It is 1/8"
larger inside diameter than the outside diameter of the duct to allow
movement of the duct inside the ring.
Figure 56: - Full Angle Ring (FAR)
HALF ANGLE RING (HAR)
A Half Angle Ring is used as a saddle in horizontal or sloped runs.
Figure 57: - Half Angle Ring (HAR)