Adapters (Dsls-Dsld) - DuraVent DuraSeal DS Installation Instructions Manual

Single wall or double wall al29-4c or 316l special gas vent for category i, ii, iii and iv type l vent low temperature venting system
Hide thumbs Also See for DuraSeal DS:
Table of Contents

Advertisement

OFFSETS (DSLS-DSLD)
1. The length of the offset is determined by strength considerations. The
maximum dimension between supports is given in Table 7 & 8, and is
applicable to all horizontal and sloped orientations. See Figure 44.
2. The minimum offset is accomplished with two elbows dircectly
connected to each other (see Figure 43 and Table 15 & 16).
3. With frequent re-support, there is no structural or operating limit to the
length of horizontal or sloped portions, providing the system meets
the capacity, pressure drop of available equipment.
4. The carrying capacity of supports and their structural attachments must
take into account the weight of the offset plus whatever vertical section
is carried by that support.
5. Height limits for supports are tabulated in Table 6.
6. The vertical sections above the offset must also be supported or
anchored and guided where necessary.
7. Anchor Plate Wall Support (WSHD) and Wall Guide (WGHD) may be
used in a varitey of ways for offset support to achieve the structural
stability of the system.
8. Re-supports must be securely anchoredtowalls, posts, or locally
fabricated rigid framework. This framework must be designed to assure
stability of supports, such as Ventilated anchor Plate (APV) supports and
Heavy Duty Wall Supports (WSHD).
9. Supports suspended by threaded rods or from small size angles or straps
are usually not satisfactory to resist bending moments due to offsets
Flue Diameter
15°
Ø (in.)
26
3/8
2 5/8
28
3/8
2 11/16
30
3/8
2 3/4
32
3/8
2 7/8
34
3/8
2 15/16
36
3/8
3
TABLE 15 - Minimum Offset for Each Elbow - DSLS
Dimensions are in inches
Flue Diameter
15°
Ø (in.)
26
1/2
3 1/4
28
1/2
3 1/4
30
1/2
3 3/8
32
1/2
3 3/8
34
1/2
3 1/2
36
1/2
3 1/2
TABLE 16- Minimum Offset for Each Elbow - DSLD
Dimensions are in inches
26
DSLS
30°
45°
90°
6 7/8
12 7/16
34 1/4
7 1/8
13
36 1/4
7 3/8
13 9/16
38 1/4
7 5/8
14 1/8
40 1/4
7 15/16
14 3/4
42 1/4
8 3/16
15 5/16
44 1/4
DSLD
30°
45°
90°
8 1/8
14 3/8
39 1/2
8 3/8
14 7/8
41 1/2
8 5/8
15 1/2
43 1/2
8 7/8
16 1/8
45 1/2
9 1/8
16 3/4
47 1/2
9 1/2
17 1/4
49 1/2
Figure 43: Minimum Offset for each Elbows

ADAPTERS (DSLS-DSLD)

TAPERED INCREASER (TIN0)
The Tapered Increaser Adapter is used for a diameter change in duct
system. Uses when there is a sufficient length for duct run available for the
size change. The TIN0 is used uses 2" of length per 1 "increment diameter
change. The TIN0 is considered to have the same load strength as a
straight duct. See Figure 45.
Figure 45: Tapered Increaser Adapter (TIN0)
ECCENTRIC TAPERED INCREASER (ETIN0)
The Eccentric Tapered Increaser Adapter is similar as the Tapered Increaser
Adapter except the smaller diameter is offset from the larger diameter.
When installed horizontally, the ETIN0 keep a flat slope unlike the TIN0.
See Figure 46.
Figure 46: Eccentric Tapered Increaser (ETIN0)
Table 7 & 8
Figure 44: Maximum Spacing
between supports for Offset