Monitoring For Bus Voltage Failure - ABB i-bus KNX IPR/S 3.5.1 Product Manual

Ip router secure
Hide thumbs Also See for i-bus KNX IPR/S 3.5.1:
Table of Contents

Advertisement

ABB i-bus
®
KNX
General
The Router features five tunneling servers, see chapter 3.4,
support both bus monitor mode and group monitor mode.
The tunneling servers can be operated in KNX Secure mode.
Alternatively to KNX standard communication (multicast), up to ten ABB IP Routers IPR/S 3.x.1 can also
communicate with each other via the unicast protocol, see chapter 4.1.2,
KNX Secure mode is not available in this case.
The power supply can be implemented via PoE (Power over Ethernet) according to IEEE 802.3af class 1
or via a supply voltage.
The ABB i-bus
network (IP discovery) and the settings to be made for unicast communication (see chapter 4.2,
bus®
An ETS app (ABB KNX Bus Update) is available for the firmware update. If KNX Secure mode is not
activated for the devices, a firmware update can also be performed with the i-bus
During the update process, the KNX bus (TP) must be connected in addition to the IP network (LAN) so
that the KNX parameters can be restored correctly. Otherwise, the update process will fail.
It must be ensured that no voltage failure (KNX or IP) occurs during the update process, otherwise the
device can be destroyed.
The device supports the KNX standard function "Monitoring for bus voltage failure." This is a network
management function, which is used by visual display systems, for example (see chapter 1.8.1,
for bus voltage
1.8.1

Monitoring for bus voltage failure

The IP Router Secure monitors the KNX TP bus for voltage failure. When the status of the bus voltage
changes, a broadcast command of the type "NetworkParameterWrite" is sent on the IP network.
The following values are sent:
Bus voltage failure: "00063301" (hex)
Bus voltage recovery: "00063300" (hex)
These telegrams can be evaluated, e.g. by a visual display system.
Type
NetworkParameterWrite
NetworkParameterWrite
8 2CDC502099D0211 Rev. A | IPR/S 3.5.1
Tool is available for the IP Router Secure devices. It allows the Routers to be found in the
®
Tool).
failure).
Use of the integrated tunneling
Info
Meaning
00 06 33 01
TP1 bus voltage failure
00 06 33 00
TP1 bus voltage recovery