Mounting And Installation; Prerequisites For Commissioning; Supplied State - ABB i-bus KNX IPR/S 3.5.1 Product Manual

Ip router secure
Hide thumbs Also See for i-bus KNX IPR/S 3.5.1:
Table of Contents

Advertisement

ABB i-bus
®
KNX
Device technology
2.4

Mounting and installation

The device is a modular DIN rail component for quick installation in distribution boards on 35 mm mounting
rails to EN 60 715.
The mounting position for the device can be selected as required.
The connection to the bus is implemented using the bus connection terminal supplied. The terminal
assignment is located on the housing.
The device is ready for operation after connection of the bus voltage and the supply voltage.
The device must be accessible for operation, testing, visual inspection, maintenance and repair in
compliance with DIN VDE 0100-520.
2.4.1

Prerequisites for commissioning

A PC with the latest version of ETS 5 and a supply voltage of 12 to 30 V DC are required in order to
commission the device. Alternatively, the device can be powered via PoE (Power over Ethernet) to IEEE
802.3af class 1.
The device is ready for operation after connection to the bus voltage and supply voltage.
Mounting and commissioning are only allowed to be carried out by electricians. The standards, directives,
regulations and specifications applicable in the related country must be observed during the planning and
setting up of electrical installations and security systems for intrusion and fire detection.
Protect the device against damp, dirt and damage during transport, storage and operation!
Only operate the device within the specified technical data!
The device should only be operated in an enclosed housing (distribution board)!
Disconnect the device from the supply of electrical power before mounting.
To avoid dangerous touch voltages which originate through feedback from differing phase conductors,
all poles must be disconnected when extending or modifying the electrical connections.
2.4.2

Supplied state

The device is supplied with the physical address 15.15.0.
All physical tunneling connection addresses are set to 15.15.100 in the supplied state. In other words, only
one tunnel is visible to the outside. The tunneling connection addresses set in the ETS will be adopted
only after the first download.
The IP address is set to automatic IP assignment (DHCP/AutoIP).
Note
The device is supplied with the option Route. This is not the default setting in the application, but it
simplifies commissioning. See chapter 3.2.1,
The programmed setting will be adopted after the first download.
Danger
Parameter window KNX ->
IPR/S 3.5.1 | 2CDC502099D0211 Rev. A 15
LAN.