Modbus Settings - Danfoss CCR3+ Operating Manual

Table of Contents

Advertisement

CCR3+ Controller
ENGLISH

13. Modbus settings

VI.GM.A2.02
Supported functions:
1. Read holding registers (0x03)
2. Write single register (0x06)
3. Write multiple registers (0x16)
1. Read holding register start addresses:
from 0 to 195:
0 – Valve output riser
(1=output closed - valve is open, 0=output open, valve
is closed)
1 – Valve output pwm riser
(valve open in percentage: 0% .. 100%, unsigned decimal)
2 – Temperature value
(valve open in percentage: 0% .. 100%, unsigned decimal)
3 – Set temperature
(temperature in °C with one decimal place precision,
unsigned decimal --> example: 529 = 52.9°C)
4 – Status(alert)*
- 0 - OK
- 1 - temp too low/high
- 4 - sensor closed (short circuit)
- 5 - sensor open (sensor not connected etc...)
Example: To get riser 6 temperature
Formula: (6(Riser) - 1) × 5 + 2 (Temp Value) = 27
180
Output 1 open/closed
181
Output 2 open/closed
182
Output 3 open/closed
183
Output 4 open/closed
184
B4 open/closed
185
RTC year
186
RTC month
187
RTC day
188
RTC hour
189
RTC minute
190
B1 open/closed
191
B2 open/closed
192
B3 open/closed
193
S0 temp
194
Ret. Set. Temp
195
Status (alert)
from 300 to 331:
300
Tret 1
301
Tret 2
302
Tret 3
303
Tret 4
304
Tret 5
305
Tret 6
306
Tret 7
307
Tret 8
308
Tret 9
309
Integration time
310
Prop factor
311
Dif. time
312
PWM interval
313
PWM min
314
Pwm max
315
Riser number
316
RTC year
317
RTC month
318
RTC day
319
RTC hour
320
RTC minute
321
Alarm delay
322
Alarm diftemp
323
Alarm type
324
Valve type
325
Valve characteristic
326
Out1
327
Out2
328
Out3
329
Out4
330
Pump protection
331
Summer mode
2. Write single register – data can be written into start addresses:
from 300 to 331
- from 400 to 435
3. Write multiple register – data can be written into start addresses:
- from 300 to 331
- from 400 to 435
from 400 to 435 :
400
Shift value 1
401
Shift value 2
402
Shift value 3
403
Shift value 4
404
Shift value 5
405
Shift value 6
406
Shift value 7
407
Shift value 8
408
Shift value 9
409
Shift value 10
410
Shift value 11
411
Shift value 12
412
Shift value 13
413
Shift value 14
414
Shift value 15
415
Shift value 16
416
Shift value 17
417
Shift value 18
418
Shift value 19
419
Shift value 20
420
Shift value 21
421
Shift value 22
422
Shift value 23
423
Shift value 24
424
Shift value 25
425
Shift value 26
426
Shift value 27
427
Shift value 28
428
Shift value 29
429
Shift value 30
430
Shift value 31
431
Shift value 32
432
Shift value 33
433
Shift value 34
434
Shift value 35
435
Shift value 36
© Danfoss | 2019.02 | 13