Download Print this page

oventrop 1158021 Commissioning Manual page 3

Advertisement

Available languages

Available languages

GB
Operating and functional components beneath the emergency actuator cover
1
2
3
General Information
______________________________________________________________________________________________
Notice
Automatic mode without the cover may only be used by the technician during commissioning.
Barrels are under high tension and can cause injuries when disassembling. To disassemble, special tools are required
And therefore this is inadmissible.
Knob not inserted = emergency function triggered
When the hood is removed, the emergency actuator automatically tests the emergency function and
moves into its safety position for safety reasons. To allow the commissioning technician to test
functionality, the emergency actuator can be switched to automatic mode by inserting the knob (1).
Remove the drive hood and then insert the knob (1) into the circuit board (2).
______________________________________________________________________________________________________________________________
Notice
Observe after installing the emergency actuator
If the emergency actuator was installed on-site, the actuating stroke must be adjusted to the valve stroke using
initialization (INIT).
______________________________________________________________________________________________
Status of the LED displays
LED beneath the emergency actuator
cover
Constantly lit
Short flashes
Long flashes
4
(1) Switch for setting the valve function
(2) Status LED display
(3) INIT key
5
(4) Receptacle for the knob during
manual adjustment
6
(5) Socket for hexagon socket key
(6) Receptacle for the knob during automatic mode
without cover during commissioning
1
2
Knob inserted = automatic mode
Meaning
Normal operation
Disabled state / voltage polarity incorrect
Installation run