Temperature Sensor Installation - Nibe POOL 11 Installation Instructions Manual

For fighter 1120/1140/1220/1240/1250

Advertisement

Available languages

Available languages

8. The sensors are connected by twin cables (for exam-
ple EKXX or LiYY) as follows for the load monitor
card, EBV– E2 see image below:
Use the following round pin sleeves for splicing be-
tween the 2-cables and sensors GT11 & GT16.
- Connect the sensor used as the flow sensor (GT
11) to terminal –E2:X4:15 and – E2: X4:16 in
the load monitor card's lower terminal block.
Disconnect the existing sensor from –X204:1 and
– X204:2 (installed on immersion heater, accessed
from the side of the heat pump).
- Connect pool sensor (GT 16) to terminal –
E2: X1:12 and –E2:X1:13 on the load monitor
card's upper terminal block.
Pressure/level monitor brine
GT15 External compensation 2
GT16 Pool temperature
X4
9. Connect Actuator Shuttle valve SV4 as follows:
- Black cable (230v signal) to spring terminal –X6:1
- Brown cable (fixed phase) to spring terminal –X6:2
- Blue cable (zero) to spring terminal –X6:3
10. Connect circulation pump P8 as follows:
- Blue cable (zero) to spring terminal –X6:3
- Yellow/green cable (earth cable) to spring terminal
–X6:4
- Brown cable (phase) to spring terminal –X6:5

Temperature sensor installation

Install the temperature sensor with cable ties with the
heat conducting paste and aluminium tape.
Then insulate with supplied insulation tape.
Note!
Sensor and communication cables must not
be placed near power cables.
-E2
EVB-Card
X1
Flow
sensor 1
Return
sensor 1
Program settings FIGHTER 1240
Select service in menu 8.1.1 to gain access to all the
menus.
Activate pool control in menu 9.2.10 by selecting
"ON". This activates the external circulation pump
and shows the pool setting menus. The pool sensor
must be connected to terminal X1:12-13 otherwise
a sensor alarm is displayed for the pool sensor.
Activate pool control in menu 8.4.4 by selecting
"ON". This allows the heat pump to heat the pool.
Select "Off" in menu 8.4.4 to prevent pool heating,
e.g. winter time.
Select the desired pool temperature in menu 8.4.1,
this temperature determines when pool heating is
stopped.
Select the desired connection difference in menu
8.4.2, this is the difference between the value in
menu 8.4.1 and when pool heating starts.
Select the desired pool charging time in menu 8.4.3,
this is how long pool heating is permitted to run.
The value is adjustable between 5 and 60 minutes.
When pool charging has started, it runs for at least
the time selected in this menu even if a heating re-
quirement arises.
Program settings FIGHTER 1250
Select service in menu 8.1.1 to gain access to all the
menus.
Activate pool control in menu 9.2.10 by selecting
"ON". This activates the external circulation pump
and shows the pool setting menus 8.4.0. The pool
sensor must be connected to terminal X1:12-13
otherwise a sensor alarm is displayed for the pool
sensor.
Activate pool heating in menu 8.4.6 by selecting
"ON". This allows the heat pump to heat the pool.
Select "Off" in menu 8.4.6 to prevent pool heating,
e.g. winter time.
Select the desired pool temperature in menu 8.4.1,
this temperature determines when pool heating is
stopped.
Select the desired connection difference in menu
8.4.2, this is the difference between the value in
menu 8.4.1 and when pool heating starts.
Select the desired pool charging time in menu 8.4.3,
this is how long pool heating is permitted to run.
The value is adjustable between 5 and 60 minutes.
When pool charging has started, it runs for at least
the time selected in this menu even if a heating re-
quirement arises.
Select desired Comp speed pool in menu 8.4.4, this
is the compressor frequency used for pool heating.
Select desired Circ-pump cont.sign. pool in menu
8.4.5 to select the speed of the internal heat medi-
um pump during pool heating.
POOL 11
GB
19