6. Technical Specifications

Isolated SmartSolar MPPT RS
Synchronised Parallel Operation
Maximum PV input power
Maximum DC charging power
Maximum DC voltage
Nominal DC voltage
Start-up voltage
MPPT voltage range
Maximum operational PV input
current
Max. PV short circuit current
reverse polarity protection (5)
PV Isolation fail level (3)
Programmable charge voltage
range (V DC) (4)
Charge voltage'absorption' (V
DC)
Charge voltage 'float' (V DC)
Maximum charge current
Battery temperature sensor
Battery voltage sense
Auxiliary output
Programmable relay (2)
Protection (1)
VE.Direct port and VE.Can port
General purpose analog/digital in
port
Remote on-off
Operating temperature range
Humidity (non-condensing)
Material & Colour
Protection category
Battery-connection
PV Connection
230 V AC-connection
Weight
Dimensions (hxwxd)
Safety
Page 23
Isolated SmartSolar MPPT RS
450/100
Yes, up to 25 units with VE.Can
9000W (450V 20A)
5000 W
SOLAR
80 – 400 V
18 A per tracker
20 A per tracker
100 kΩ
CHARGER
Minimum : 36 V
Maximum : 69.5 V
Default : 57.6 V
Default : 55.2 V
GENERAL
c - g (see below)
Yes, 2x
-40 to +65°C (fan assisted cooling)
max 95%
ENCLOSURE
steel, blue RAL 5012
Two M8 bolts torque to 14 N.m
Two terminal connectors (2.5-16 mm
Screw terminals 13 mm² (6 AWG)
7.9 kg
440 x 313 x 126 mm
STANDARDS
450 V
300 V
120 V
100 A
Yes
Yes
No
Yes
Yes
Yes
IP22
2
) torque to 1.2 N.m
?
Technical Specifications