APPLIANCE CONNECTION TO THE FLUE AND FUEL PRODUCTS EVACUATION

The fl ue must receive the discharge from only one heat generator. The direct discharge towards closed
spaces is forbidden, even with clear sky.
The direct discharge of the fuel products must be at roof and the smoke pipe must have the features
provided in the "Chimney or individual fl ue" section.

CHIMNEY CAP

The chimney cap must comply with the following requisites:
have an internal section equivalent to that of the chimney;
have useful outlet section not lower than double the chimney internal section;
be built in order to avoid rain, snow, foreign bodies penetrating the chimney and in order that, in case
of winds in any direction and inclination, the discharge of the fuel products is assured.
be positioned in a way to guarantee an adequate dispersion and dilution of the fuel products and,
however, outside the refl ux area in which the formation of counter-pressure occurs.
Such area has diff erent dimensions and confi guration depending on the covering inclination angle, it is
therefore necessary to adopt the minimum heights indicated in the fi gure layouts below.
The chimney cap must not have mechanical suction means.
FLAT ROOF
SLOPING ROOF
H min
MOUNTING PHASES
50 cm
> 5 m
< 5 m
fi gure 3.13
distance < A
ß
fi gure 3.14
50 cm
< 5 m
50 cm over the ridge
REFLUX AREA
refl ux area height
Chapter 3
15