Polarization time : Page “Sensor” ..................22 Output testing : Page “Test” ....................23 VIII. Factory Menu ........................24 Selection of the language....................24 Selection of the sensor ......................24 Selection of the range......................25 CE Compliance certificate ......................26 ® Programming instructions of the SYCLOPE INDIG’O...
The information provided in this document must be strictly observed. SYCLOPE Electronique S.A.S. declines all responsibility in cases where failure to comply with the instructions of this documents is observed.
Use of the document Page 5/28 2) Storage and transport It is important to store and transport your SYCLOPE INDIG’O ® in its original packaging in order to minimize risk of damage. Furthermore, the package must be stored in an environment that is protected against humidity and exposure to chemical products.
Redox potential, Ozone, etc… by means of sensors and controls of suitable actuators in the context of the possible uses described in this manual. All other uses are considered to be non-conforming and must therefore be forbidden. SYCLOPE Electronique S.A.S. will not be responsible in any case for any damages that result from such uses.
Reference of the product Limitation of dangerous substances Range of power supply EC certified Values of the maximum current Country of origin Classify protection Manufacturer square code Identification of the manufacturer Serial number Identification label ® Programming instructions of the SYCLOPE INDIG’O...
According to European directive 2002/95/EC, this symbol means that the SYCLOPE ® controller is designed in compliance with the restrictions on hazardous substances INDIG’O...
Key “Esc” : Allow to return at the permanent display Key “+” : Allow to increment a value or change a setting Key “-” : Allow to decrement a value or change a setting ® Programming instructions of the SYCLOPE INDIG’O...
Showing the actives alarms Showing status of the control. Auto or STOP M/A Indicator Set point Value to reach Dosage Percent of control on the metering unit Output Value sent to the PLC ® Programming instructions of the SYCLOPE INDIG’O...
I<3,7 mA Sensor out of range Sensor out of range Stop dosing or short circuit short circuit. I>20 mA Disconnected Bad connection or Stop dosing sensor in default defective sensor ® Programming instructions of the SYCLOPE INDIG’O...
Human/Machine interface Page 12/28 4) Internal connections Reference: CEN0000 with 4-20 mA analog input References: CEN0001 and CEN0005 with pH or ORP input ® Programming instructions of the SYCLOPE INDIG’O...
IV. Navigation into the menus 1) Accessing to the menus ® The programming interface of the SYCLOPE INDIG’O is based on 3 differents levels: Setting Menu: to program the working settings such set point, alarms… Configuration Menu: to configure the machine such flow switch, analog output…...
To start the control, press the key “START/STOP” Free Cl Free Cl 2,09 2,09 mg/l mg/l Set point : 2,00 mg/l Set point : 2,00 mg/l Dosage : 0,00% Dosage : Output : 4,187 mA Output : 4,187 mA ® Programming instructions of the SYCLOPE INDIG’O...
Slope after calibration in mA/mg/l or in mV/pH @Standard (Version mA) Correcting factor after calibration % Offset (Version mV) Offset after calibration in mV After calibrating, a message appears to tell you the calibration status. ® Programming instructions of the SYCLOPE INDIG’O...
Page 16
Slope : 1,19 mA/mg/l Slope : 1,19 mA/mg/l Set point : 2,00 mg/l @Standard : Can’t be calibrated @Standard : Reset with Dosage : during polarization factory calibration Output : 4,187 mA ® Programming instructions of the SYCLOPE INDIG’O...
If difference is 0.5 (< to 1) then Controlling value = 50% If difference is 0.25 (< to 1) then Controlling value = 25% Setpoint : 2,00 mg/l Dosage : Output : 6,400 mA ® Programming instructions of the SYCLOPE INDIG’O...
In the 4-20 mA version, if the Hysteresis dosing mode is set, the control range should be set in the “Control” page of the Setting Menu instead of the Xp value in proportional dosing mode. This value is also expressed in the measuring unity (For example, mg/l). ® Programming instructions of the SYCLOPE INDIG’O...
Page 20
Xp : 1 mg/l value in % Time Hysteresis threshold mode Value in mg/l High Threshold Hysteresis Setpoint Low Threshold Hysteresis Temps Controlling Setpoint : 1,50 mg/l value in % Hyst. : 1 mg/l Time ® Programming instructions of the SYCLOPE INDIG’O...
Min. time Minimum time of an action on the dosing unit 0………5 s R1 set = P is for control 1Dosage R1 relay R1 or R2 R2 set = R is for control 1Alarme ® Programming instructions of the SYCLOPE INDIG’O...
This page allow you to define the polarization time of the sensor. After the power supply or after a default on the sensor, the controller wait during the time set before controlling. During this time, a pictogram is displayed on the main screen: ® Programming instructions of the SYCLOPE INDIG’O...
R1 relay Working test of P Open or Close Open 1Dosage R2 relay Working test of R Off or On 1Alarme Output I Working test of I 0…20 mA 0,00 OUT1 ® Programming instructions of the SYCLOPE INDIG’O...
This area allow you to choose the measuring sensor. Refer to the version, to see the possibilities: Default Name Signification Version Setting range value Free Chlorine Active Chlorine Total Chlorine CLO2 Version 4-20 mA BCDMH Bromine Free Chlorine DBDMH Bromine Free Bromine Sensor Choice of the sensor Ozone Turbidity ® Programming instructions of the SYCLOPE INDIG’O...