1MRK 505 382-UEN B
4.3.2
Communication set-up 670/650 series 2.2
Application Guide
Analog and binary signal transfer for line differential protection
IEC10000231 V1 EN-US
Figure 17:
An example of analog input configuration via PCM600

Configuration of output signals

There are a number of signals available from the LDCM that can be connected to
the virtual binary inputs (SMBI) and used internally in the configuration. The
signals appear only in the Signal Matrix Tool (SMT) where they can be mapped to
the desired virtual input.
The signal name is found in the Object Properties window by clicking on the input
signal number in SMT. Connect the signals to the virtual inputs as desired (see
Figure
18
Section 4
M12022-93 v4