Ld0.Rescmmxu1 Residual Current Limit Supervision; Ld0.Resvmmxu1 Residual Voltage Limit Supervision; Protection Functions; Ld0.Ledptrc1 Global Protection Signals - ABB Relion 615 Series Point List Manual

Line differential protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

1MRS756879 D
2.3.4.2
Table 15:

LD0.RESCMMXU1 Residual current limit supervision

IEC 61850 name
LD0.RESCMMXU1
.HiAlm.stVal
.HiWrn.stVal
2.3.4.3
Table 16:

LD0.RESVMMXU1 Residual voltage limit supervision

IEC 61850 name
LD0.RESVMMXU1
.HiAlm.stVal
.HiWrn.stVal
2.3.5
2.3.5.1
Table 17:

LD0.LEDPTRC1 Global protection signals

IEC 61850 name
LD0.LEDPTRC1
.Op.general
.Op.phsA
.Op.phsB
.Op.phsC
.Str.general
.Str.phsA
.Str.phsB
.Str.phsC
2.3.5.2
Table 18:

LD0.TRPPTRC1 Global conditioning (1)

IEC 61850 name
LD0.TRPPTRC1
.Op.general
.Tr.general
RED615
Point List Manual
LD0.RESCMMXU1 Residual current limit supervision
SA name
HIGH_ALARM
HIGH_WARN
LD0.RESVMMXU1 Residual voltage limit supervision
SA name
HIGH_ALARM
HIGH_WARN

Protection functions

LD0.LEDPTRC1 Global protection signals
SA name
-
-
-
-
-
-
-
-
LD0.TRPPTRC1 Global conditioning (1)
SA name
-
-
Description
High alarm
High warning
Description
High alarm
High warning
Description
Global protection signals
-General Operate
-phsA Operate
-phsB Operate
-phsC Operate
-General Start
-phsA Start
-phsB Start
-phsC Start
Description
Operate input signal
Trip output signal
Section 2
DNP3 data mappings
Values
1=Alarm
1=Warning
Values
1=Alarm
1=Warning
Values
1=Operate
1=Operate
1=Operate
1=Operate
1=Start
1=Start
1=Start
1=Start
Values
1=Operate
1=Trip
17