Panduit PANZONE PZRFE4U Instructions Manual
Panduit PANZONE PZRFE4U Instructions Manual

Panduit PANZONE PZRFE4U Instructions Manual

Raised floor enclosures

Advertisement

Quick Links

© Panduit Corp. 2014
The following items are included with PZRFE4/8/12
(1) Enclosure with
(4) Grommet Sleeves
PZRFE4U
Installation:
1. Select the installation location ensuring there are no obstacles to interfere with the installation.
2. Mount the four support brackets under the enclosure by placing one on each pedestal mount bracket by attaching the U-bolt and nut
around the pedestal (See Figure 2.1). Refer to Figures 4.1 through 4.3 for adjustment to various pedestal sizes. Use the magnetic ruler to
measure the correct mounting location for each support bracket. Point them towards the center making a cross from the corners (See
Figure 2.2). Ensure that the plate is allowed to pivot from side-to-side. Note: If Grid Runner is placed above pedestal plate, then the
mounting assembly must be removed from plate and reconnected with the mounting assembly under the pedestal plate (See Figure 2.3).
3. Push CoolBoot Assemblies inside enclosure (See Figure 3.1) and then insert the enclosure in the desired floor tile.
Figure 2.1
Figure 2.2
FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
Part Numbers: PZRFE4U, PZRFE8U, PZRFE12U & PZRFC
(4) Support Brackets, with
Washers and Nuts
PZRFE8U
Figure 2.3
P
Z
Raised Floor Enclosures
AN
ONE
INSTRUCTIONS CM469D
(1) Magnetic Ruler
(4) Bonding Bolts
Required Tools
PZRFE12U
Distance from bottom of pedestal head plate to top of mounting brackets.
Part Number
Mounting Bracket Depth Below Floor
With Optional Cover
Enclosure Load Rating
Figure 3.1
Mounting assembly connected
under pedestal mount plate.
Page 1 of 5
Optional Components: PZRFC
(1) Set of Keys
*10mm Socket
(1) Lockable Enclosure Cover
*7/16" Socket
Mounting Depth Table
PZRFE4U PZRFE8U PZRFE12U
18 lb
(+ .25" Tolerance)
5"
8.5"
12"
10.5"
14"
7"
36 lb
54 lb

Advertisement

loading

Summary of Contents for Panduit PANZONE PZRFE4U

  • Page 1 Raised Floor Enclosures Part Numbers: PZRFE4U, PZRFE8U, PZRFE12U & PZRFC INSTRUCTIONS CM469D © Panduit Corp. 2014 The following items are included with PZRFE4/8/12 Optional Components: PZRFC (1) Set of Keys (1) Magnetic Ruler (4) Bonding Bolts (4) Support Brackets, with...
  • Page 2 4. The PZRFE*U may be mounted to 7/8” square or up to 2” diameter round pedestals by adjusting the engagement of the U-Bolt. 7/8” square pedestal Figure 4.1 1 1/2” diameter pedestal Figure 4.2 2” diameter pedestal Figure 4.3 For Technical Support: www.panduit.com/resources/install_maintain.asp Page 2 of 5...
  • Page 3 6. Once all four corners and mounting holes are aligned in the correct orientation (See Figure 6.1), fasten the enclosure to the pedestal mount- ing brackets using the supplied M6 X 12mm bonding bolts (See Figure 6.2). Figure 5.2 Figure 5.1 Figure 6.2 Figure 6.1 M6 X 12mm Bonding Bolts Top View (4) Places For Technical Support: www.panduit.com/resources/install_maintain.asp Page 3 of 5...
  • Page 4 Note: Install all cabling in accordance with NEC article 300.22 and Article 800. Cool Boot Application Parts List: (A) - Fabric & (B) - Hook and loop cinch tie Cinch material in center to separate wire bundles. For Technical Support: www.panduit.com/resources/install_maintain.asp Page 4 of 5...
  • Page 5 Once the knockouts have been successfully removed, drop the cover The cover’s locking mechanism tabs should be aligned in the knockout geometry as shown in Figure 10. For Instuctions in Local Languages E-mail: and Technical Support: tech support@panduit.com Fax: www.panduit.com/resources/install_maintain.asp (866)405-6654 www.panduit.com...
  • Page 6 This page intentionally left blank.

This manual is also suitable for:

Panzone pzrfe8uPanzone pzrfe12uPanzone pzrfc