Input Registers (3X References) - Siemens SIPROTEC4 7UM62 Manual

Multifunctional machine protection, communication module, modbus, bus mapping
Table of Contents

Advertisement

Standard mapping 3-2
3.3

Input registers (3X references)

Designation of the
Register
SIPROTEC objects
30001
IA S2=
30002
IB S2=
30003
IC S2=
30004
Va-b=
30005
Vb-c=
30006
Vc-a=
30007
P =
30008
Q =
30009
f =
30010
I2 =
Θ
Θ
30011
/
trip =
30012
<user-defined>
30013
IA S1=
30014
IB S1=
30015
IC S1=
30016
<user-defined>
30017
<user-defined>
30018
<user-defined>
30019
<user-defined>
30020
<user-defined>
30021
<user-defined>
1 Available from version V02.02.01 of Standard mapping 3-2.
3-12
• Ref. to chap. 1.2.3 for additional notes regarding scaling of measured values.
Operat. meas. current A side 2
Operat. meas. current B side 2
Operat. meas. current C side 2
Va-b
Vb-c
Vc-a
P (active power)
Q (reactive power)
Frequency
I2 (negative sequence)
Temperature rise for warning and trip
not pre-allocated
Operat. meas. current A side 1
Operat. meas. current B side 1
Operat. meas. current C side 1
1
not pre-allocated
1
not pre-allocated
1
not pre-allocated
1
not pre-allocated
1
not pre-allocated
1
not pre-allocated
Comments
Scaling
(32767 corresponds to ...)
327.67 %
327.67 %
327.67 %
327.67 %
327.67 %
327.67 %
327.67 %
327.67 %
327.67 Hz
327.67 %
327.67 %
-
327.67 %
327.67 %
327.67 %
-
-
-
-
-
-
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
Internal
object no.
724
725
726
624
625
626
641
642
644
606
801
-
721
722
723
-
-
-
-
-
-

Advertisement