Register 40129: Diagnosis - Siemens SIPROTEC4 7UM62 Manual

Multifunctional machine protection, communication module, modbus, bus mapping
Table of Contents

Advertisement

Standard mapping 3-1
2.4.3

Register 40129: Diagnosis

Designation of the
Register
SIPROTEC objects
0
40129/2
Device OK
1
40129/2
<user-defined>
2
40129/2
ProtActive
3
40129/2
Error Sum Alarm
4
40129/2
Alarm Sum Event
5
40129/2
Relay PICKUP
6
40129/2
Relay TRIP
7
40129/2
Operat. Cond.
8
40129/2
<user-defined>
9
40129/2
<user-defined>
10
40129/2
<user-defined>
11
40129/2
<user-defined>
12
40129/2
<user-defined>
13
40129/2
<user-defined>
14
40129/2
<user-defined>
15
40129/2
Data valid
2-14
• Registers are write-protected.
• The contents of these registers are also readable using function "Diagnostics"
(function code 7), subfunction "Return Diagnostic Register" (subfunction code 2).
• Ref. to chap. "Bus specific parameters" in the manual "SIPROTEC Communication
module, Modbus - Communication profile" regarding signalisation of "Data invalid"
15
(register 40129/2
).
1.
A write access is rejected with exception code 03 (ILLEGAL_DATA_VALUE).
1
Comments
1 = Update of the device replica in the SIPROTEC
device completed after initial start or restart
not pre-allocated
1 = At least one protection function is active
1 = Error with a summary alarm ON
1 = Alarm summary event ON
1 = Relay PICKUP (group signal)
1 = Relay GENERAL TRIP command
1 = Suitable measured quantities are present at the
device inputs (V > 0.05 * V
10 Hz < Freq. < 70 Hz)
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
not pre-allocated
1 = Data in the Modbus message are valid.
(This indication is created by the Modbus slave;
not available in DIGSI and not relocatable.)
, I > 0.05 * I
and
nom
nom
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
Internal
object no.
51
-
52
140
160
501
511
5002
-
-
-
-
-
-
-
-