2.2.20 Registers 10088 to 10091: Binary inputs
Designation of the
Register
SIPROTEC objects
10088
Ext 1 Gen.TRP
10089
Ext 2 Gen.TRP
10090
Ext 3 Gen.TRP
10091
Ext 4 Gen.TRP
2.2.21 Registers 10092 to 10093: Inadvertent energisation protection
Designation of the
Register
SIPROTEC objects
10092
50/27 picked up
10093
50/27 TRIP
2.2.22 Register 10094: Trip coil monitor
Designation of the
Register
SIPROTEC objects
10094
FAIL: Trip cir.
2.2.23 Registers 10095 to 10096: Inverse undervoltage protection
Designation of the
Register
SIPROTEC objects
10095
Vp< picked up
10096
Vp< TRIP
2.2.24 Registers 10097 to 10099: Startup supervision of motors
Designation of the
Register
SIPROTEC objects
10097
48 Rot. locked
10098
48 picked up
10099
48 TRIP
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
Comments
1 = External trip 1: General TRIP
1 = External trip 2: General TRIP
1 = External trip 3: General TRIP
1 = External trip 4: General TRIP
Comments
1 = 50/27 picked up
1 = 50/27 TRIP
Comments
1 = 74TC Failure Trip Circuit
Comments
1 = Inverse Undervoltage Vp< picked up
1 = Inverse Undervoltage Vp< TRIP
Comments
1 = 48 Rotor LOCKED after Lock. Rotor Time
1 = 48 Starting time supervision picked up
1 = 48 Starting time supervision TRIP
Standard mapping 3-1
Internal
object no.
4537
4557
4577
4597
Internal
object no.
5547
5548
Internal
object no.
6865
Internal
object no.
6525
6527
Internal
object no.
6822
6823
6821
2-9