2.2.12 Registers 10051 to 10058: Frequency protection

Designation of the
Register
SIPROTEC objects
10051
81-1 picked up
10052
81-2 picked up
10053
81-3 picked up
10054
81-4 picked up
10055
81-1 TRIP
10056
81-2 TRIP
10057
81-3 TRIP
10058
81-4 TRIP

2.2.13 Registers 10059 to 10063: Overexcitation protection

Designation of the
Register
SIPROTEC objects
10059
24 warn
10060
24-1 picked up
10061
24-2 picked up
10062
24 th.TRIP
10063
24-2 TRIP

2.2.14 Registers 10064 to 10066: Reverse power protection

Designation of the
Register
SIPROTEC objects
10064
32R picked up
10065
32R TRIP
10066
32R+SV TRIP

2.2.15 Registers 10067 to 10070: Forward power supervision

Designation of the
Register
SIPROTEC objects
10067
32F< picked up
10068
32F> picked up
10069
32F P< TRIP
10070
32F P> TRIP
SIPROTEC Modbus - Bus mapping 7UM62
C53000-L1840-C009-03
Comments
1 = 81-1 picked up
1 = 81-2 picked up
1 = 81-3 picked up
1 = 81-4 picked up
1 = 81-1 TRIP
1 = 81-2 TRIP
1 = 81-3 TRIP
1 = 81-4 TRIP
Comments
1 = 24 V/f warning stage
1 = 24-1 V/f> picked up
1 = 24-2 V/f>> picked up
1 = 24 TRIP of thermal stage
1 = 24-2 TRIP of V/f>> stage
Comments
1 = 32R picked up
1 = 32R TRIP
1 = 32R TRIP with stop valve
Comments
1 = 32F P< stage picked up
1 = 32F P> stage picked up
1 = 32F P< stage TRIP
1 = 32F P> stage TRIP
Standard mapping 3-1
Internal
object no.
5232
5233
5234
5235
5236
5237
5238
5239
Internal
object no.
5367
5370
5373
5372
5371
Internal
object no.
5096
5097
5098
Internal
object no.
5126
5127
5128
5129
2-7