The device must be connected to the VNR-terminal on the unit controller according to the polarity.
Figure 14 shows the VNR terminal on the unit controller.

Figure 14: VNR connection for the remote display

Before connecting cables make sure the power supply complies with the hardware requirements.
Separate the terminal cables from the power supply cables, the outputs and the power connections.
2.9.3

Single commands

Press the SET button to display the target setpoint. In programming mode, this
allows to select a parameter or to confirm an operation.
Press the RESET button and hold for 5 seconds to reset any lockouts if the
current state of the controller allows for it to be reset.
(UP) To view the fast access menu. In programming mode, this browses the
parameter codes or increases the displayed value.
(DOWN) In programming mode, this browses the parameter codes or decreases
the displayed value.
(SERVICE) To enter the service and alarm menu.
Hold for 3 seconds to start a manual defrost or terminate an active defrost.
Table 10: Single commands
Double commands – Entering programming level 1 "Pr1"
2.9.4
Press simultaneously for about 3 seconds to lock (PoF) or unlock (Pon) the
keyboard.
Press simultaneously to leave the programming mode or menu. On submenus
rtC and EEV this combination allows to go back to the previous level.
Press simultaneously for about 3 seconds to access the first level of
programming mode.
Table 11: Double commands
The device provides 2 programming levels:
Pr1 with direct access
Pr2 protected with a password (intended for experts)
2.9.5

How to program the parameters (Pr1 and Pr2)

Access pre-
program level
Access
program level
Access Pr1
Select item
Show value
Modify
C6.1.9/0219/E
VNR connection for
the remote display
Press simultaneously for about 3 seconds to access the pre-
programming level. The message rtC (real time clock) appears.
or
Press the Up or Down key until the message Par appears.
Press the SET button to enter the program level. First parameter
C01 appears.
or
Select the parameter or submenu using the arrows.
Press the SET button.
or
Use the arrows to modify the value.
15