Troubleshooting
Fault
No output voltage, "Inverter"
LED lights up red, display
shows "ENIR TEMP Shut-
down"
No output voltage, "Inverter"
LED lights up red, display
shows "H.S. TEMP Shut-
down"
No output voltage, "Inverter"
LED lights up red, display
shows "BAT. TEMP Shut-
down"
No charging current
No charging current,
"Charger" and "AC Grid"
LEDs are off
No charging current, "Alarm"
LED lights up red, display
shows "UV Alert"
The device constantly
restarts
NOTE
I
If you have detailed questions on the battery specifications,
please contact the battery manufacturer.
100
Cause
Overheating
Incorrect frequency
No 230 V power
Overheating
No connection to the battery
CombiPower
Remedy
Check the ventilation grilles
and clean them if necessary
Improve the ventilation
Set up the device somewhere
cooler
Check the configured fre-
quency
Check the 230 V power sup-
ply
Check the wiring
Switch off the consumer
units.
Let the inverter cool down
and ensure better ventilation
Check the battery wiring