7 iSolarCloud App
7.7.2 Protection Parameter
User with this account can only view protection parameters, and default
•
values of these protection parameters have been set according to
corresponding grid standards.
To modify protection parameters, contact SUNGROW to obtain the
•
advanced account and corresponding password.
table 7-8 Protection parameter description
P P a a r r a a m m e e t t e e r r
Country(region)
Grid type*
Protection level
Single-level protection value
Multi-level protection values
Protection recovery value
*If the country code is "China", the grid type can be set to power plant/non-power plant.
Set the grid type to correct value according to definitions of power plant
scenario and non-power plant scenario. Otherwise, the inverter will run
abnormally or even be damaged, and SUNGROW shall not be held liable for any
damage caused.
Power plant scenario: The inverter is applied to a power plant whose
•
capacity is greater than 1 MW, or to a power plant that feeds power into the
grid at the voltage greater than 35KV and connects to the public power grid
at the voltage of 10KV.
Non-power plant scenario: application scenarios other than the power plant
•
scenario.
The definitions come from the national code "NB/T 32004", "GB-T19964".
table 7-9 Single-level Protection Parameters Explanation
P P a a r r a a m m e e t t e e r r
AC under-voltage single stage protection value
AC over-voltage single stage protection value
50
D D e e f f i i n n i i t t i i o o n n / / S S e e t t t t i i n n g g d d e e s s c c r r i i p p t t i i o o n n
Depends on the location of the plant
Depends on the grid standards
The level of protection of over/under-voltage and
over/under-frequency
See
"table 7-9 Single-level Protection Parameters
Explanation"
See
"table 7-10 Multi- level Protection Parameters
Explanation"
See
"table 7-11 Description of protection recovery
parameters"
D D e e f f a a u u l l t t
110.0V
276.0V
User Manual
R R a a n n g g e e
23V ~ 230V
220V ~ 322V