7 iSolarCloud App

7.7.2 Protection Parameter

User with this account can only view protection parameters, and default
values of these protection parameters have been set according to
corresponding grid standards.
To modify protection parameters, contact SUNGROW to obtain the
advanced account and corresponding password.
table 7-8 Protection parameter description
P P a a r r a a m m e e t t e e r r
Country(region)
Grid type*
Protection level
Single-level protection value
Multi-level protection values
Protection recovery value
*If the country code is "China", the grid type can be set to power plant/non-power plant.
Set the grid type to correct value according to definitions of power plant
scenario and non-power plant scenario. Otherwise, the inverter will run
abnormally or even be damaged, and SUNGROW shall not be held liable for any
damage caused.
Power plant scenario: The inverter is applied to a power plant whose
capacity is greater than 1 MW, or to a power plant that feeds power into the
grid at the voltage greater than 35KV and connects to the public power grid
at the voltage of 10KV.
Non-power plant scenario: application scenarios other than the power plant
scenario.
The definitions come from the national code "NB/T 32004", "GB-T19964".
table 7-9 Single-level Protection Parameters Explanation
P P a a r r a a m m e e t t e e r r
AC under-voltage single stage protection value
AC over-voltage single stage protection value
50
D D e e f f i i n n i i t t i i o o n n / / S S e e t t t t i i n n g g d d e e s s c c r r i i p p t t i i o o n n
Depends on the location of the plant
Depends on the grid standards
The level of protection of over/under-voltage and
over/under-frequency
See
"table 7-9 Single-level Protection Parameters
Explanation"
See
"table 7-10 Multi- level Protection Parameters
Explanation"
See
"table 7-11 Description of protection recovery
parameters"
D D e e f f a a u u l l t t
110.0V
276.0V
User Manual
R R a a n n g g e e
23V ~ 230V
220V ~ 322V