Recommended Rack Configurations
Chapter
4
4 Installation

4.1 PDU Mounting Bracket Installation (KIT-MBVPT-1B)

The installation of PDU mounting bracket kit (KIT-MBVPT-1B) for the AFCO, TRIPPLITE, and CRENLO racks
extends the PDUs farther back in the rack to allow for more room for the CMA and enclosure.
Note: For recommended vertical rack rail settings, see:
page 11.
Table 31: Procedure Info
Required Tools
Torx T15 Screwdriver
1. Install the bottom side bracket using the provided hardware.
a) Locate the two screw holes at the bottom of the back side of the PDU.
b) Align the flat bracket with the two bottom PDU screw holes as shown.
Figure 6: Flat Bracket (bottom)
4.1
PDU Mounting Bracket Installation (KIT-MBVPT-1B)
Vertical Rack Rail Settings
Required Parts
Two Flat Brackets
• Two Right-Angle Brackets
• Two Backer Plates
• M6 x 16 Hex Cap Screws
• M6 Fender Washers
• M6 Hex Nut with Nylon Lock
22
4
Installation
on
# of People
Required
1