5

Outdoor Unit Installation

5.1

Outdoor Unit Installation Instructions

Step 1: Select installation location.
The outdoor unit should be installed in a location that meets the following
requirements:
f Place the outdoor unit as close to the indoor unit as possible.
f Ensure that there is enough room for installation and maintenance.
f The air inlet and outlet must not be obstructed or exposed to strong
wind.
f Ensure the location of the unit will not be subject to snowdrifts,
accumulation of leaves or other seasonal debris. If possible, provide
an awning for the unit. Ensure the awning does not obstruct airflow.
f The installation area must be dry and well ventilated.
f There must be enough room to install the connecting pipes and
cables and to access them for maintenance.
Strong wind
Fig. 17.
f The area must be free of combustible gases and chemicals.
f The pipe length between the outdoor and indoor unit may not exceed
the maximum allowable pipe length.
f If possible, DO NOT install the unit where it is exposed to direct
sunlight.
f If possible, ensure the unit is located far away from your neighbours
property so that the noise from the unit will not disturb them.
f If the location is exposed to strong winds (for example: near
a seaside), the unit must be placed against the wall to shelter it from
the wind. If necessary, use an awning. (See Fig. 17 & 18)
f Install the indoor and outdoor units, cables and wires at least 1 metre
from televisions or radios to prevent static or image distortion.
Depending on the radio waves, a 1 metre distance may not be enough
to eliminate all interference.
Fig. 18.
Climate 5000 SCI – 6720887422 (2019/07)
Step 2: Install outdoor unit.
Fix the outdoor unit with anchor bolts (M10)
Fig. 19.
Strong wind
• Ensure to remove any obstacles that may block air circulation.
• Ensure you refer to the length specifications to ensure there is
enough room for installation and maintenance.
Split Type Outdoor Unit
(Refer to Fig 20, 21, 22, 26 and Table 5)
Fig. 20.
Strong wind
Fig. 21.
>600 mm
Fix with bolts