Accessories; Outdoor Unit Installation - Bosch CLIMATE 5000 VRF RDCI Series Installation Manual

All dc inverter outdoor units
Hide thumbs Also See for CLIMATE 5000 VRF RDCI Series:
Table of Contents

Advertisement

Refrigerant replenishment
Additional refrigerant must be added prior to turning the units on.
Correct refrigerant charge must be calculated using the guidelines
within this manual.
On completion of the refrigerant installation you must record the
exact additional refrigerant charge.
Electric wiring
When selecting the size of the power supply cable, consult
this manual along with national regulations. When selecting
communication wiring follow guidelines set out in this manual.
When installing communication cabling, ensure you read electrical
installation guideline in this manual.
Test Run
Before operation, remove the six pieces of PE foaming which are
used at the rear of the unit for protecting the condenser. Be careful
not to damage the fins. Otherwise, the heat exchange performance
may be affected.
Prior to test run, ensure the power has been on for a minimum of
12 hours.

3. ACCESSORIES

Table.3-1
Model
All of units
Name
Outdoor unit
1
installation manual
Outdoor unit owner's
1
manual
Indoor unit owner's
1
manual
1 (8HP, 10HP)
90° elbow
2 (12HP~
16HP)
Seal plug
8
Connective pipe
1
accessory
(used in 8HP~16HP)
Connective pipe
1
accessory
(used in 8HP~16HP)
Connective pipe
1
accessory
(used in 8HP, 10HP, 12HP)
Connective pipe
1
accessory
(used in 14HP, 16HP)
Connective pipe
2
accessory
Screw bag
1
1
Cable clip kit
(Optional)
RDCI Series – All DC Inverter Outdoor Units
Outline
Function
___________
Upon completion leave
with customer
On completion leave with
customer
________
For connecting pipes
________
For pipe cleaning
Connect to the high-pressrue
gas balance side
Connect to the liquid
pipe side
Connect to the high-
pressure gas pipe side
Connect to the high-
pressure gas pipe side
Connect to the low-pressure
gas pipe or liquid pipe side
(used in 12HP)
________
Stored for service
For cable fastening

4. OUTDOOR UNIT INSTALLATION

4.1 Outdoor unit combination
Table.4-1
Max Qty.
HP
Mode
of indoor
unit
8
8HP×1
13
10
10HP×1
16
12
12HP×1
20
14
14HP×1
23
16
16HP×1
26
18
8HP+10HP
29
20
10HP+10HP
33
22
10HP+12HP
36
24
10HP+14HP
39
Table.4-2
Max Qty.
HP
Mode
of indoor
unit
44
14HP×2+16HP
64
46
14HP+16HP×2
64
48
16HP×3
64
50
64
8HP+10HP+16HP×2
52
64
10HP×2+16HP×2
54
64
10HP+12HP+16HP×2
4.2 Dimensions of outdoor unit
4.3 Selecting installation location
Ensure that the outdoor unit is installed in a well-ventilated location.
Ensure that the noise and exhaust ventilation of the outdoor
unit does not affect the neighbours of the property owner or its
surroundings.
Where possible ensure the shortest pipe route.
Ensure that the outdoor unit is installed in a cool location without
direct sunshine exposure or direct radiation.
ACCESSORIES | 3
Max Qty.
HP
Mode
of indoor
unit
26
10HP+16HP
43
28
14HP×2
46
30
14HP+16HP
50
32
16HP+16HP
53
34
10HP×2+14HP
56
36
10HP×2+16HP
59
38
63
10HP+12HP+16HP
40
64
10HP+14HP+16HP
42
14HP×3
64
Max Qty.
HP
Mode
of indoor
unit
56
64
10HP+14HP+16HP×2
58
14HP×3+16HP
64
60
14HP×2+16HP×2
64
62
14HP+16HP×3
64
64
16HP×4
64
Unit: mm
Fig. 4-1
6 720 862 437 (2016/10)