Refrigerant Piping Connection; Notes On Pipe Length And Elevation - Bosch Climate 5000 SCI Series Installation Manual

Middle static pressure duct type air conditioner
Hide thumbs Also See for Climate 5000 SCI Series:
Table of Contents

Advertisement

Units with a pump
1. Remove the test cover.
Fill the water pan with 2 litres of water.
Test cap
Fig. 32.
Fig. 33.
2. Turn on the unit in COOLING mode. You will hear the drain pump.
Check whether the water is discharged properly (a 1-minute lag
is possible, depending on the length of the drain pipe). Check
whether water leaks from the joints.
3. Turn off the air conditioner and put the cap back on.
Climate 5000 SCI – 6720887422 (2019/07)
7
Safety Precautions
• All field piping must be completed by a licensed technician and must
comply with the local and national regulations.
• When the air conditioner is installed in a small room, measures
must be taken to prevent the refrigerant concentration in the room
from exceeding the safety limit in the event of refrigerant leakage. If
the refrigerant leaks and its concentration exceeds its proper limit,
hazards due to lack of oxygen may result.
• When installing the refrigeration system, ensure that air, dust,
moisture or foreign substances do not enter the refrigerant circuit.
Contamination in the system may cause poor operating capacity,
high pressure in the refrigeration cycle, explosion or injury.
• Ventilate the area immediately if there is refrigerant leakage during
the installation. Leaked refrigerant gas is both toxic and flammable.
Ensure there is no refrigerant leakage after completing the installa-
tion work.
7.1
Ensure that the length of the refrigerant pipe, the number of bends,
and the drop height between the indoor and outdoor units meets the
requirements shown in Table 8:
Type of model
Split Inverter
Table 8. The Maximum Length and Drop Height Based on Models
Refrigerant Piping with Twin Indoor Units
When installing multiple indoor units with a single outdoor unit, ensure
that the length of the refrigerant pipe and the drop height between
the indoor and outdoor units meet the requirements illustrated in the
following diagram:
Stow tube
The drop height
between indoor unit
and outdoor unit
must be less than or
Fig. 34.
• Oil traps
If the outdoor unit is installed higher than the indoor unit:
-It is recommended that vertical suction risers not be upsized.
Proper oil return to the compressor should be maintained with
suction gas velocity. If velocities drop below 7.62 m/s, oil return will
be decreased. An oil trap should be installed every 6 m of vertical
suction line riser. (See Fig. 35)

Refrigerant Piping Connection

WARNING

Notes On Pipe Length and Elevation

Capacity
(Btu/h)
<15K
≥15K - <24K
≥24K - <36K
≥36K - ≤60K
(Unit: m)
Outdoor unit
L
H2
equal to 20 m
The line branch pipe
CAUTION
Refrigerant Piping Connection
Length of
Maximum
piping
drop height
25
10
30
20
50
25
65
30
Indoor unit
L1
The drop height
between two
H1
indoor units must
be less than or
L2
equal to 500 mm
Indoor unit
15