Wiring
3. Connect the u-lugs to the terminals
Match the wire colours/labels with the labels on the terminal block.
Firmly screw the u-lug of each wire to its corresponding terminal.
4. Clamp down the cable with the cable clamp.
5. Insulate unused wires with electrical tape. Keep them away from any
electrical or metal parts.
6. Re-install the cover of the electric control box.
8.2

Indoor Unit Wiring

1. Prepare the cable for connection.
a. Using wire strippers, strip the rubber jacket from both ends of the
signal cable to reveal about 150 mm of the wire.
b. Strip the insulation from the ends of the wires.
c. Using a wire crimper, crimp the u-lugs to the ends of the wires.
2. Remove the cover of the electric control box on your indoor unit.
3. Connect the u-lugs to the terminals.
Match the wire colours/labels with the labels on the terminal block.
Frmly screw the u-lug of each wire to its corresponding terminal.
Refer to the serial number and wiring diagram located on the cover
of the electric control box.
Control box
Fig. 46.
Magnetic ring (if supplied and packed with the accessories)
1 2 3
Fig. 47.
20
Pass the belt through the hole
of the magnetic ring to fix it on
the cable
CAUTION
• While connecting the wires, please strictly follow the wiring dia-
gram.
• The refrigerant circuit can become very hot. Keep the interconnec-
tion cable away from the copper tube.
4. Clamp down the cable with the cable clamp. The cable must not be
loose or pull on the u-lugs.
5. Reinstall the electric box cover .
Using the wire controller to set external static pressure (some
models)
• You can use the unit's automatic airflow adjustment function to set
external static pressure.
• Automatic airflow adjustment is the volume of blow-off air that has
been automatically adjusted to the quantity rated.
1. Make sure the test run is done with a dry coil. If the coil is not dry,
run the unit for 2 hours in FAN ONLY mode to dry the coil.
2. Check that both power supply wiring and duct installation have
been completed Check that any closing dampers are open. Check
that the air filter is properly attached to the air suction side passage
of the unit.
3. If there is more than one air inlet and outlet, adjust the dampers so
that the airflow rate of each air inlet and outlet conforms with the
designed airflow rate. Ensure the unit is in FAN ONLY mode. Press
and set the airflow adjustment button on the remote control to
change the airflow rate from H or L.
4. Set the parameters for automatic airflow adjustment. When the air
conditioning unit is off, perform the following steps:
• Press "COPY".
• Press "+" or "-" to select the AF.
Fig. 48.
• Press "CONFIRM". The air conditioning unit will then start the fan
for automatic airflow adjustment.
ON will flash when the fan is on during
automatic airflow adjustment.
Fig. 49.
CAUTION
• DO NOT adjust the dampers when automatic airflow adjustment is
active.
After 3 to 6 minutes, the air conditioning unit stops operating once
automatic airflow adjustment has finished.