Standard Configuration Options
The standard configuration options are very similar to those of other
®
LogTag
recorder products and include settings such as
start
method,
pre-start
recording,
start
delay, and password.
Figure 2: TRED30-16R Standard Configuration Options
For detailed information about each parameter please read the section
about Configuring a LogTag
User Guide or press F1 for help.
TRED30-16R Start Options
During configuration with LogTag
the TRED30-16R starts taking temperature readings.
... via
Push button
start: The recorder will start taking
l
temperature readings after you have gone through a specific start
sequence of pressing and releasing the
button (see
Starting the Recorder
... via
Date/Time start
: The recorder will start taking
l
temperature readings at the date and time you specify (local
time).
When you choose the push button start option, you can select to
record
pre-start readings
or
If you configure the TRED30-16R to start after a delay period, the
l
recorder will not immediately record temperature readings after
you have pressed
START
timer instead, and record readings only after the timer has ended.
It will, however, continue to take pre-start readings, if enabled.
You cannot combine a date/time start with pre-start readings or the
start delay function.
Alarm Configuration Options
The TRED30-16R can display an alarm if either of the configured
alarm trigger conditions have been met. This is indicated on the
display by showing the Alarm Indicator ( ) and the Day Alarm
Marker for today (
).
Distributed by MicroDAQ
Page 5 of 17
User
logging interval
and duration,
®
®
for logging in LogTag
Analyzer's
®
Analyzer you can decide when
START
/CLEAR/STOP
on page 9).
Begin recording after a
delay.
, but start a countdown
/CLEAR/STOP
ID,
Each alarm trigger condition consists of a threshold temperature
value, an activation type (which can be instant, consecutive or
1
accumulative
If an alarm trigger condition requires readings to exceed an upper
threshold temperature it is called an upper alarm. If an alarm trigger
condition requires readings to go below a lower threshold it is called a
lower alarm.
The alarm triggering structure in the recorder supports many
different alarm trigger configurations.
For example, a possible alarm trigger configuration could be:
Upper alarm is triggered when the temperature is 10°C or above
l
for an accumulative time of 10 hours.
Lower alarm is triggered when the temperature is -0.5°C or below
l
continuously for 1 hour.
All alarm trigger conditions are configured using LogTag
please see the
Once an alarm has triggered, the alarm indicator ( ) remains
shown until the alarm is cleared (see
The day alarm marker
turns off and the marker for the previous day is shown (
indicate the alarm was registered against what is now the previous
day. When midnight passes next, this marker will move to
so on.
Once an alarm event occurred, all alarm counters are reset, and the
alarm processing starts again. Accumulative or consecutive alarms
will re-trigger, if the alarm conditions are met again, and the Alarm
Indicator ( ) and the Day Alarm Marker (
again.
Alarm Re-triggering
1
Instant = one temperature reading is above (below) the threshold
l
Consecutive = temperature readings are above (below) the threshold for the
l
time defined in the activation delay without interruption
Accumulative = temperature readings are above (below) the threshold for the
l
total time defined in the activation delay time, but may not necessarily be
sequential.
www.MicroDAQ.com
TRED30-16R Product User Guide, Revision 1.4, copyright © 2004-2017,
) and a delay time, if it is not an instant alarm.
Figure 3: Sample Alarm Configuration Settings
Standard Configuration Options
Clearing an Alarm
remains shown until midnight, then it
(603) 746-5524
LogTag
®
Analyzer,
above.
on page 11).
) to
and
) will be shown once
®
Recorders
. All rights reserved.
Need help?
Do you have a question about the TRED30-16R and is the answer not in the manual?