Appendix D. Foundation Fieldbus Communication
D.4.2 Password
A password must be entered to change XMT1000 system parameters. This can be done using Foundation Fieldbus.
There are different levels of security for different Passwords ( Admin or Operator ). Please see the standard manual for
more detail on password levels. Figure 25 below shows the password fields in the XMT1000 Resource Block.
Attention! Before entering a password, make sure the XMIT_TB transducer block is in active mode.
To Enter configuration mode, complete the following steps:
1. Select the Resource Block > Others tab.
2. Select SYSTEM_OPT_TYPE and set to Option FI .
3. Select SYSTEM_REQ_LEVEL and set to Admin or Operator .
4. Enter the Admin or Operator password into the SYSTEM_REQ_PASS field.
5. Select Cancel from the SYSTEM_REQ_CMD drop down box.
6. Select Login from the SYSTEM_REQ_CMD drop down box.
7. Click on the Write Changes button.
8. Verify that S1:In Config Mode appears on XMT1000 display. You should now be able to edit fields with Admin
privileges.
64
Figure 25: Password Fields in XMT1000 Resource Block
PanaFlow™ XMT1000 User's Manual