Four And Six Point Loading; Dm 4 And 6 Point Loads Weight Distribution; Center Of Gravity - York SUNLINE 2000 DM 048 Technical Manual

Single package gas/electric units and single package air conditioners
Table of Contents

Advertisement

A
44
7
/
8
D
X
APPROXIMATE

CENTER OF GRAVITY

FRONT OF UNIT
FIGURE 10 - FOUR AND SIX POINT LOADING
TABLE 30: DM 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT
DM036 Cooling/ Electric
DM036N04
DM036D06
DM036N08
DM036D10
DM048 Cooling/ Electric
DM048(D,N)06
DM048(D,N)10
DM060 Cooling/ Electric
DM060D06
DM060N08
DM060(D,N)10
DM072 Cooling/ Electric
DM072D06
DM072N08
DM072(D,N)10
TABLE 31: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
X
Y
40
BACK OF UNIT
82
/
1
4
B
C
CONDENSER COIL
END OF UNIT
Y
4-Point Loading (lb)
TOTAL
A
B
565
125
123
605
134
132
615
137
134
625
139
136
635
141
138
615
137
134
665
148
145
685
152
149
640
142
140
690
153
150
700
155
153
710
158
155
720
160
157
770
171
168
780
173
170
790
175
172
6 TON
40-¾"
44"
19-¾"
22"
A
44
7
/
8
F
X
APPROXIMATE
CENTER OF GRAVITY
FRONT OF UNIT
C
D
A
157
160
84
168
171
90
171
174
91
173
177
93
176
179
94
171
174
91
184
188
99
190
194
102
178
181
95
191
195
102
194
198
104
197
201
105
200
203
107
214
218
114
216
220
116
219
223
117
036-21502-003-A-1105
BACK OF UNIT
82
1
/
4
B
E
D
Y
6-Point Loading (lb)
B
C
D
83
82
104
89
88
112
90
89
113
92
91
115
93
92
117
90
89
113
98
96
123
100
99
126
94
93
118
101
100
127
103
101
129
104
103
131
106
104
133
113
112
142
114
113
144
116
114
146
Unitary Products Group
C
CONDENSER COIL
END OF UNIT
E
F
105
107
113
114
115
116
117
118
119
120
115
116
124
126
128
129
119
121
129
130
131
132
132
134
134
136
144
145
146
147
147
149

Hide quick links: