The default switching frequency is 3 kHz for Open-loop and RFC-A.
The maximum cable length is reduced from that shown in Table 5-18, Table 5-19 and Table 5-20 if
high capacitance motor cables are used. For further information, refer to section 4.4.2 High-
capacitance / reduced diameter cables on page 57.
5.1.23
Minimum resistance values and peak power rating for the braking resistor
at 40 °C (104 °F)
Table 5-21 Braking resistor resistance and power rating (100 V)
Model
01100017
01100024
02100042
02100056
Table 5-22 Braking resistor resistance and power rating (200 V)
Model
01200017
01200024
01200033
01200042
02200024
02200033
02200042
02200056
02200075
03200100
04200133
04200176
94
Minimum
resistance*
130
68
Minimum
resistance*
130
68
45
22
Unidrive M100 to M400 Frame 1 to 4 Power Installation Guide
Instantaneous
power rating
kW
1.1
2.2
Instantaneous
power rating
kW
1.1
2.2
3.3
6.0
Continuous
power rating
kW
0.25
0.37
0.75
1.1
Continuous
power rating
kW
0.25
0.37
0.55
0.75
0.37
0.55
0.75
1.1
1.5
2.2
3
4
Issue Number: 5