Adjusting The Output Current To 0 Or 4 Ma; Adjusting The Output Current To 20 Ma - Baelz Automatic 373-E66 Series Operating Instructions Manual

Actuator for modulating duty
Table of Contents

Advertisement

Operating Instructions

8.4.3 Adjusting the output current to 0 or 4 mA

● Move the actuator to the position at which the output current is to be 4 mA
● Manually rotate the black adjustment wheel (2) against the white actuator gear wheel (1), or use a screw-
driver for rotating, to adjust the output current to 3.98–4.02 mA (for two-wire connection).

8.4.4 Adjusting the output current to 20 mA

● Move the actuator to the position at which the output current is to be 20 mA
● Use the span selector (3) to adjust the output current to 20 +/- 0.02 mA
● Check the setting and repeat the adjustment if necessary
Technical specifications subject to change
W. Bälz & Sohn GmbH & Co.
Phone +49 (0)7131 15 00 0
Fig. 27: Adjusting the output current to 20 mA
Koepffstrasse 5
Fax +49 (0)7131 15 00 21
Fig. 26: Adjusting the output current to 0 or 4 mA
Electronic position transmitter
Span
Observe copyright protection DIN 34
74076 Heilbronn
www.baelz.de
Page 30/37
BA 373-E66