Setting The Electronic Position Transmitter; Setting To Normal Mode "N; Setting To Reverse Mode "R - Baelz Automatic 373-E66 Series Operating Instructions Manual

Actuator for modulating duty
Table of Contents

Advertisement

Operating Instructions

8.4 Setting the electronic position transmitter

The position transmitter can be operated in two modes. The operating modes are selected with the mode
selector (1).
Normal mode "N":
● rising characteristic
when rotating the gear wheel
clockwise or retracting connecting
rod or
● falling characteristic
when rotating the gear wheel
counter-clockwise or extending
connecting rod
Reverse mode "R":
● rising characteristic
when rotating the gear wheel
counter-clockwise or extending
connecting rod, or
● falling characteristic
when rotating the gear wheel
clockwise or retracting
connecting rod

8.4.1 Setting to Normal mode "N"

● Adjust the travel on the switching and signalling unit (refer to chapters 6.2 and 6.3)
● Turn the selector (1) on the electronic position transmitter fully clockwise to stop "N".
Make sure the mode selector (1) is always set to the end position to prevent a malfunction of the position transmit-
ter (the lower and upper range values cannot be adjusted). Turn the screw carefully to avoid damage to the stop in
the end position.

8.4.2 Setting to Reverse mode "R"

● Adjust the travel on the switching and signalling unit (refer to chapters 6.2 and 6.3)
● Turn the selector (1) on the electronic position transmitter fully counter-clockwise to stop "R".
Make sure the mode selector (1) is always set to the end position to prevent a malfunction of the position transmit-
ter (the lower and upper range values cannot be adjusted). Turn the screw carefully to avoid damage to the stop in
the end position.
Technical specifications subject to change
W. Bälz & Sohn GmbH & Co.
Phone +49 (0)7131 15 00 0
Output current
Rotation angle
Span setting on delivery
Minimum span
Maximum span
Fig. 26-1: Adjustment range for measuring
span in normal mode
Output current
Rotation angle
Span setting on delivery
Minimum span
Maximum span
Fig. 26-3: Adjustment range for measuring
span in reverse mode
Koepffstrasse 5
Fax +49 (0)7131 15 00 21
BA 373-E66
Electronic position transmitter
Span
Fig. 26-2: Selector for mode (1)
and span
Electronic position transmitter
Span
Fig. 26-4: Selector for mode (1)
and span
Observe copyright protection DIN 34
74076 Heilbronn
www.baelz.de