7.10 Changing the preset signal range for the set point

The positioning electronics can be preset using measurement points without the need for an input signal. For ad-
justment to the actuator, refer to chapter 7.5 Calibrating the positioning electronics to the travel.
Adjusting the 4...20 mA or 2...10 V signal
Configuration of DIP switches S1:
S1.1
S1.2
X
X
Figure 20: Set point 4-20mA, 2-10V
● Apply voltage to terminals 54 and 55 of the positioning electronics
● Measure the voltage between measurement points 3 and 6
● Use potentiometer P1 to adjust the voltage to 2.0 V
● Measure the voltage between measurement points 3 and 4
● Use potentiometer P2 to adjust the voltage to 10.0 V
Adjusting the 0...20 mA or 0...10 V signal
Configuration of DIP switches S1:
S1.1
S1.2
X
X
Figure 21: Set point 0-20mA, 0-10V
● Apply voltage to terminals 54 and 55 of the positioning electronics
● Measure the voltage between measurement points 3 and 6
● Use potentiometer P1 to adjust the voltage to 0.0 V
● Measure the voltage between measurement points 3 and 4
● Use potentiometer P2 to adjust the voltage to 10.0 V
Technical specifications subject to change
W. Bälz & Sohn GmbH & Co.
Phone +49 (0)7131 15 00 0
S1.3
S1.4
S1.5
X
X
X
S1.3
S1.4
S1.5
X
X
X
Koepffstrasse 5
Fax +49 (0)7131 15 00 21
ON
OFF
ON
OFF
BA 373-E66
Observe copyright protection DIN 34
74076 Heilbronn
www.baelz.de
mail@baelz.de
Page 25/37
Germany

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

373-e66-150-22373-e66-080-25

Table of Contents