Operating Instructions

7.2 Mounting the positioning electronics

Mechanical assembly is done at the factory. After the actuator has been mounted on the valve and the switching
and signalling unit have been adjusted, set the potentiometer zero point. as described in chapter 6.4.

7.3 Electrical connection

Risk of electric shock!
Danger
Power connection and commissioning of the actuator require specialized technical knowledge regarding
the erection of electric power installations (according to DIN VDE 0100), of the accident prevention regula-
tions and of the special requirements for commissioning the linear actuator. These procedures must be
performed by qualified personnel only. Failure to heed this warning may result in death, serious injury or
substantial material damage!
● When making the electrical connection, be sure that the power supply is turned OFF! Ensure protection
against unintentional reconnection to power!
● For wiring and connection of the electrical lines, observe the DIN/VDE regulations for the erection of electric
power installations and the regulations of the local energy supplier!
● Check compliance of the line voltage and the line frequency with the specifications on the identification
label of the actuator and on the identification label of the actuator motor.
● Always select the line cross section so as to match the actuator's power consumption and the required line
length. The permissible wire cross section is 0.8...2.5 mm
● Disconnection from power supply, system side: to disconnect the power supply to the actuator and de-ener-
gize the actuator for maintenance and calibration/adjustment, install a suitable main breaker in the system,
which guarantees that all poles (except the grounding conductor) are disconnected when turning off. This
main breaker must be lockable when switched off and must be protected against unintentional reconnection
to power.
● Mains protection, system side: max. 6 A.
Technical specifications subject to change
W. Bälz & Sohn GmbH & Co.
Phone +49 (0)7131 15 00 0
Koepffstrasse 5
Fax +49 (0)7131 15 00 21
(AWG 28...12).
2
Observe copyright protection DIN 34
74076 Heilbronn
www.baelz.de
Page 19/37