Assigning The Control Function Second Setpoint Sp.2 To A *Digital Input At 6X90B(-Y) /1 /4 /4-I. S2.D; Assigning The Control Function Open To A *Digital Input At 6X90B(-Y) /1 /4 /4-I; Assigning The Control Function Close To A *Digital Input At 6X90B(-Y) /1 /4 /4-I; Assigning The Control Function Stop To A *Digital Input At 6X90B(-Y) /1 /4 /4-I - Baelz Automatic 6490B Device Manual

Microprocessor-based controller mcelsitron, universal three-position step controller
Table of Contents

Advertisement

Device manual
3.21 Assigning the control function SECOND SETPOINT SP.2 to a *digital input
at 6x90B(-y) /1 /4 /4-i
Selection:
In case of a "high" signal at the selected input the controller switches to the second setpoint.
See also 3.25 Important information about setting digital inputs
3.22 Assigning the control function OPEN to a *digital input
Selection:
In case of a "high" signal at the selected input the actuator is set to permanent OPEN.
See also 3.25 Important information about setting digital inputs
3.23 Assigning the control function CLOSE to a *digital input
Selection:
In case of a "high" signal at the selected input the actuator is set to permanent CLOSE.
See also 3.25 Important information about setting digital inputs
3.24 Assigning the control function STOP to a *digital input
Selection:
In case of a "high" signal at the selected input the actuator is set to permanent STOP and persists in its current
position. No OPEN or CLOSE pulses are given.
See also 3.25 Important information about setting digital inputs

3.25 Important information about setting digital inputs

- Possibly not all the adjustable software settings are supported by your device version.
See 8. Ordering number. The software allows settings from 1 ... 5 in 3.21 to 3.24, even if your
controller has got no or one single digital input.
- If one of the digital inputs is assigned to multiple control functions, e.g. CL.d = 1 and St.d = 1, only
the function with the highest priority will be executed if active:
1. STOP (highest priority), 2. CLOSE, 3. OPEN, 4. SP.2

3.26 Adjusting the digital inputs for the usage with INBAS

If the keywords "DIOPEN", "DICLOSE", "DISTOP" and "DISP2" shall be used, following adjustments for the
digital inputs have to be set: OP.d = 1, CL.d = 2, St.d = 3, S2.d = 5.
INBAS-version ≥ 1.5 has to be used for 6490B / 6490B-y / 6590B controller types.

3.27 Calibration correction for the process variable input PV

With C.CO, a calibration correction for the actual value can be defined.
Setting range: 0 to ± scope of the measuring range [phys. units]
C.CO = 0
W. Bälz & Sohn GmbH & Co.
0 :
No digital input is selected.
1 ... 5 : Defines the number of the digital input to activate the second setpoint SP.2 .
0 :
No digital input is selected.
1 ... 5 : Defines the number of the digital input to activate an OPEN command.
0 :
No digital input is selected.
1 ... 5 : Defines the number of the digital input to activate a CLOSE command.
CLOSE function is assigned to digital input 1 by factory.
0 :
No digital input is selected.
1 ... 5 : Defines the number of the digital input to activate a STOP command
:
no calibration correction - the measured process variable is used.
Koepffstraße 5
D-74076 Heilbronn
6490B / 6490B-y / 6590B
S2.d
at 6x90B(-y) /1 /4 /4-i
at 6x90B(-y) /1 /4 /4-i
at 6x90B(-y) /1 /4 /4-i
C.CO
Telefon (07131) 1500-0
Page 23
OP.d
CL.d
St.d
* option
Telefax (07131) 1500-21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6490b-y6590bMcelsitron 6490b-yMcelsitron 6490bMcelsitron 6590b

Table of Contents