To obtain the required backup time, the batteries may be connected in parallel. In this case, each battery
string must be connected to a separate BCB.
Note
Only properly trained personnel shall maintain or operate the BCB.

6.7 Battery Installation And Connection

6.7.1 Battery Installation

1. Before installation, check the battery appearance to ensure that there is no damage, inspect and count the
accessories, and carefully read this manual and the user manual or installation instruction provided by the
battery manufacturer.
2. There shall be a clearance of 10mm between the vertical sides of the batteries for the smooth flow of the air
around the batteries.
3. Certain clearance shall be maintained between the battery top and the underside of the layer above it to
facilitate battery monitoring and maintenance.
4. The batteries shall be installed from the bottom layer upwards to avoid high gravity center. The battery shall
be properly installed and protected from vibration and shock.
5. Measure the battery voltage, and calibrate the battery voltage after UPS startup.

6.7.2 Battery Connection

1. When the battery cabinet is installed on a raised floor, the battery power cables and optional BCB control
cables can enter the UPS cabinet through the cabinet bottom. If the UPS and battery cabinet are installed side
by side on a solid floor, these cables can be led into the UPS cabinet through the cable entry holes on the lower
part of the battery cabinet.
2. When multiple battery strings are used, they shall be connected in series and then in parallel. Before
applying load and power-up, be sure to measure the total voltage of the battery strings and make sure that it
is correct. The negative and positive terminals of the battery must be connected to the corresponding
negative and positive battery terminals of the UPS according to the labels on the battery and UPS. Reverse
battery connection may cause explosion, fire, battery damage, UPS damage, and personal injury.
3. After connecting the battery cables, install an insulating shroud on each terminal.
4. When connecting the cables between the battery terminals and the BCB, connect from the BCB side first.
5. The bending radius of the cable shall be larger than 10D, where D is the outer diameter of the cable.
6. After cable connection, it is prohibited to pull the battery cables or the cable terminals.
7. Do not cross the battery cables during connection, and do not tie the battery cables together.
8. Refer to Figure 6-1 for the battery cable connection.
Liebert APM 150 Integrated UPS Single Module And Parallel System
Chapter 6 Battery
User Manual
51