Wire the Burner

Wire the burner per National Electric Code ANSI/
NFPA 70 (Canada CSA C22.1) and all applicable
codes and requirements. High and Low gas pressure
switches must be installed and wired in accordance
with manufacturer's instructions. Wire the burner in
compliance with all instructions and diagrams provided
by the appliance manufacturer. Verify operation
of all controls in accordance with the appliance
manufacturer's guidelines.
Wiring diagrams included with literature package.
Explosion, Fire, Scald, and Asphyxiation Hazard
All heating appliances must have HIGH LIMIT
protection to interrupt electrical power and shutdown
the burner if operating or safety controls fail and cause
a runaway condition.
Follow the appliance manufacturer's wiring diagrams
f
and note all required safety controls.
Typical safety controls include high temperature or
f
pressure limits, low water cutoffs, pressure relief valves
and blocked flue sensing switches.
Do not tamper with, or bypass, safety controls.Verify
f
all limit and safety controls are installed and functioning
correctly, as specified by the manufacturer, applicable
safety standards, codes and all authorities having
jurisdiction.
If a safety control is not functioning properly, shut off all
f
main electrical power and gas supply to the burner and
call a qualified service agency immediately.
Keep Service Access Covers Securely Installed
All covers must be securely in place to prevent electrical
shock, protect against injury from moving parts and
prevent damage from external elements.
Maximum fuse size for the 120 Vac 60 Hz electrical power
supply to the burner is 20 Amps.
All covers or service access plates must be in place at all
times except during maintenance and service.
This applies to all controls, panels, enclosures, switches,
and guards or any component with a cover as part of
its design.
20
— Section: Installation Instructions
Electrical Shock Hazard
Electrical shock can cause severe personal
injury or death.
Line voltage neutral shall not be used as a
f
substitute for ground.
Disconnect electrical power before
f
installing or servicing the burner.
Provide ground wiring to the burner, metal
f
control enclosures and accessories. A
good ground is required to maintain a
good flame sensing.
Use a ground fault interrupt if grounding of
f
the burner can be compromised.
Fire or Explosion Hazard
Can cause severe injury, death, or property
damage.
The control can malfunction if it gets wet,
f
leading to accumulation of gas.
Never install where water can flood, drip
f
or condense on the control.
Never use a control that has been wet -
f
replace it.
Explosion, Fire and Asphyxiation
Hazard
Do not tamper with, or bypass, safety
controls. If a safety control is not
functioning properly, shut off all main
electrical power and gas supply to the
burner and call a qualified service agency
immediately.
Fire or Explosion Hazard
Can cause severe injury, death, or property
damage.
When replacing a 7800 series control on a
Beckett CG gas burner the "JR1" jumper must
be clipped for a 4 sec proof of flame time.
Electromagnetic Interference
Operation of this burner in a residential area may cause
interference, in which case the user will be required to
correct the interference.
CG15, CG25, CG50 Burner Manual, Form No. 6104BCG50