Table 2 — Gas Supply Piping Capacity
Schedule 40 metallic pipe with 0.50 psi or less inlet pressure and 0.30" W.C. pressure drop
Maximum capacity in cubic feet of gas per hour (CFH). Natural gas with 0.60 specific gravity. Pipe size (inches) IPS
Pipe Length (ft.)
0.75"
10
20
30
40
50
60
70
80
90
100
125
150
175
200
For other inlet pressures and pressure drops, see NFPA 54 for Natural Gas piping or NFPA58 for LP Gas Piping.
14
— Section: Inspect & Prepare Installation Site
1.0"
1.25"
278
520
1050
190
350
730
152
285
590
130
245
500
115
215
440
105
195
400
96
180
370
90
170
350
84
160
320
79
150
305
72
130
275
64
120
250
59
110
225
55
100
210
1.5"
2.0"
2.5"
1600
3050
4800
1100
2100
3300
800
1650
2700
760
1450
2300
670
1270
2000
610
1150
1850
560
1050
1700
530
990
1600
490
930
1500
460
870
1400
410
780
1250
380
710
1130
350
650
1050
320
610
980
CG15, CG25, CG50 Burner Manual, Form No. 6104BCG50
3.0"
4.0"
8500
17500
5900
12000
4700
9700
4100
8300
3600
7400
3250
6800
3000
6200
2800
5800
2600
5400
2500
5100
2200
4500
2000
4100
1850
3800
1700
3500

Hide quick links: