5.3

Installing the power supply module

Introduction
The power supply module is optional for the ET 200MP distributed I/O system, and can be
deployed as needed.
The power supply module increases the power on the backplane bus and thus permits the
use of additional modules.
Requirements
The mounting rail is installed.
An I/O module located before the power supply (PS) module has a U connector inserted at
back right.
Tools required
Screwdriver with 4.5 mm blade
Installing the power supply module
1. Place the U connector at the back right on the power supply (PS) module (see following
2. Install the power supply module on the mounting rail.
3. Pivot the power supply module towards the back.
4. Open the front cover.
5. Disconnect the power cable connector from the power supply module.
6. Fasten the power supply module (torque 1.5 Nm).
7. Insert the already wired-up power cable connector into the power supply module.
For a description on how to wire the power cable connector refer to the section Connecting
the supply voltage on the power supply module (Page 59).
ET 200MP Distributed I/O System
System Manual, 01/2013, A5E03723484-01
picture).
Figure 5-4
Installing the power supply module
5.3 Installing the power supply module
Installation