Siemens SIMATIC ET 200MP System Manual page 35

Hide thumbs Also See for SIMATIC ET 200MP:
Table of Contents

Advertisement

In the following example calculation the power budget for a configuration is determined.
Table 4- 2
Sample calculation for power budget
Modules
IM 155-5 PN ST
Analog output module AQ 4xU/I ST
Analog input module AI 8xU/I/RTD/TC ST
Digital output module DQ 32x24VDC/0.5A ST
Digital input module DI 32x24VDC HF
Analog output module AQ 4xU/I ST
Total requirement
Power budget
Result: The power budget is positive (9.9 W > 0). If it had been negative (< 0 W), then an
additional power supply module would have been required.
Up to 12 I/O modules may be operated on the power segment of the IM 155-5 PN ST
interface module, as long as the total power drawn by the I/O modules is < 14 W.
Reference
Further information on the performance values (power feed, power consumption) of the
interface module, of the power supply module, and of the I/O modules can be found in the
Product Manuals of the respective modules.
ET 200MP Distributed I/O System
System Manual, 01/2013, A5E03723484-01
Incoming power to the backplane bus
Power from the backplane bus
Result
Application planning
4.2 Power budget calculation
Power
14 W
0.6 W
0.7 W
1.1 W
1.1 W
0.6 W
4.1 W
14 W - 4.1 W = 9.9 W
35

Advertisement

Table of Contents
loading