VAV CONFIGURATION REQUIREMENTS (continued)
Control
Number
Variable Required
COOLING CONTROL (continued)
[CV] LPSTART_TYPE
[CV] P_PO_TIME
[CV] CND_LO_LIM
[CV] LEAD_LAG_ENABLE 0 to disable
[CV] ECONO_TYPE
[CV] CND_ECON_SYNC
Value
Control
Required
Number
0, 1, or 2
0 to disable
With 1 or 2
141-144 [DI] LP1-4
190-193 [DO] LLSV1-4,
0 to disable or
1-255 seconds
141-144 [DI] LP1-4
190-193 [DO] LLSV1-4
0 to disable or
1-255 seconds
3
1 to enable
ECONOMIZER
0, 1, or 2
0 to disable
With 1 or 2
1
8
9
With 1
52
With 2
0 or 1
0
1
214
29
PM7600B INPUT AND OUTPUT OPTIONS
Dependent
Variable Required
See below.
None
[CV] LPSTART_DELAY
None
[CV] PO_TIME
None
[AI] CNDTMP
None
None
See below.
None
[CV] ECON_SELECT
[AI] DA_TMP
[SP] PRG_DAC_SP or
[AI] DAC_SP
[SP] PRG_DAC_CB or
[AI] DAC_CB
[SP] MIN_ECONO_POS
[AO] A_ECON
[CV] ECON_MOTOR_SPEED
207-208, [DO] ECON+, ECON- Must be
See below.
None
[DO] CNDPMP
[CV] ECONO_TYPE
PM7600B
Dependent
Value Required
N/A
≥ LP1,
1 minimum
configured
≥ LLSV1,
1 minimum
configured.
0-255 seconds
N/A
1 minimum
configured.
0 to disable or
1-255 seconds.
N/A
Must be
configured.
N/A
N/A
N/A
1, 2 or 3
Must be
configured.
30° to 90° F
Set
PRG_DAC_SP
to Unprog.,
0° F or -18° C.
1° to 50° F
Set
PRG_DAC_CB
to Unprog. or 0.
0-100%
Must be
configured.
30-160 seconds
configured.
N/A
Must be
configured.
1 or 2
63-4309—2