PM7600B
TROUBLESHOOTING/ALARMS
Failure
Symptoms
Cause
W7600 A-F does a
control lockout
Remedies
Failure
Symptoms
Cause
W7600 A-F does a
control lockout
Remedies
Failure
Symptoms
Cause
W7600 A-F does a
control lockout
Remedies
63-4309—2
AO (Analog Output) configu-
ration file lost.
Analog Output Config Has Been
Lost on the S7600A display.
Checksum error in analog output
configuration database.
W7600A-F continues to operate
normally except for algorithms
that use analog outputs. The ana-
log output are driven to 0 mA.
Reconfigure all outputs using ex-
isting archived database from
ZM7601/ZM7603 Software. File
group in ZM7601/ZM7603 Soft-
ware to download W7600A-F is
All Files or the selected indepen-
dent file Analog Output Configu-
ration.
DO (Digital Output) configu-
ration file lost.
Digital Output Config Has Been
Lost displayed on the S7600A.
Checksum error in digital output
configuration database.
W7600A-F continues to operate
normally except for algorithms
that use digital outputs. Digital
outputs are driven to the de-ener-
gized position.
Reconfigure all digital outputs
using existing archived database
from ZM7601/ZM7603 Soft-
ware. File group in ZM7601/
ZM7603 Software to download
W7600A-F is All Files or the se-
lected independent file Digital
Output Configuration.
RA (Remote Analog) configu-
ration file lost.
Remote Analog Config Has Been
Lost displayed on the S7600A.
Checksum error in remote analog
configuration database.
W7600A-F continues to operate
normally, except for algorithms
that use remote analogs. Remote
analog points lose their configura-
tion parameters, disabling these
algorithms.
Reconfigure all remote analogs
using existing archived database
from ZM7601/ZM7603 Soft-
ware. File group in ZM7601/
ZM7603 Software to download
W7600A-F is All Files or the se-
lected independent file Remote
Analog Configuration.
Failure
Symptoms
Cause
W7600 A-F does a
control lockout
Remedies
Failure
Symptoms
Cause
W7600 A-F does a
control lockout
Remedies
Failure
Symptoms
Cause
W7600 A-F does a
control lockout
Remedies
54
RD (Remote Digital) configu-
ration file lost.
Remote Digital Config Has Been
Lost displayed on the S7600A.
Checksum error in remote digital
configuration database.
W7600A-F continues to operate
normally, except for algorithms
that use remote digitals. Remote
digital points lose their configura-
tion parameters, disabling these
algorithms.
Reconfigure all remote digitals
using existing archived database
from ZM7601/ZM7603 Soft-
ware. File group in ZM7601/
ZM7603 Software to download
W7600A-F is All Files or the se-
lected independent file Remote
Digital Configuration.
PD (Pseudo Digital) configura-
tion file lost.
Pseudo Digital Config Has Been
Lost displayed on the S7600A.
Checksum error in pseudo digital
configuration database.
W7600A-F continues to operate
normally, except for algorithms
that use pseudo digital points. PD
is used for datasharing the TOD
ON/OFF status.
Reconfigure pseudo digital points
utilizing archived database from
ZM7601/ZM7603 Software. File
group in ZM7601/ZM7603 Soft-
ware to download W7600A-F is
All Files or the selected indepen-
dent file Pseudo Digital Configu-
ration.
PA (Pseudo Analog) configura-
tion file lost.
Pseudo Analog config Has Been
Lost displayed on the S7600A.
Checksum error in pseudo analog
configuration database.
W7600A-F continues to operate
normally, except for algorithms
that use pseudo analog points. The
pseudo analog points are used for
setpoint changes from the S7600A
Keyboard Display Module.
Reconfigure pseudo analogs uti-
lizing archived database from
ZM7601/ZM7603 Software. File
group in ZM7601/ZM7603 Soft-
ware to download W7600A-F is
All Files or the selected indepen-
dent file Pseudo Analog Configu-
ration.