Honeywell PM7600B Manual page 20

Network compatible variable air volume program module for w7600
Table of Contents

Advertisement

PM7600B
PM7600B INPUT AND OUTPUT OPTIONS
DIGITAL INPUTS (continued)
Point Name
Compressor 2 Oil Pressure
Compressor 3 Oil Pressure
Compressor 4 Oil Pressure
Low Pressure 1 Safety
Low Pressure 2 Safety
Low Pressure 3 Safety
Low Pressure 4 Safety
Compressor 1 Shed
Compressor 2 Shed
Compressor 3 Shed
Compressor 4 Shed
Outdoor Air Enthalpy
High
Dirty Filter
System Switch On
Alarm Silence
Heat Failure
Fan Motor Safety
63-4309—2
S7600
W7600 Input
Label
Control Number
OIL_F2
138
OIL_F3
139
OIL_F4
140
LP1
141
LP2
142
LP3
143
LP4
144
SHED_1
145
SHED_2
146
SHED_3
147
SHED_4
148
OD_ENT
149
FILTER
150
SYS_SW
151
AL_SIL
152
HT_FL
154
FN_FL
155
Functional Description
As with OIL_F1, lock out Compressor 2.
As with OIL_F1, lock out Compressor 3.
As with OIL_F1, lock out Compressor 4.
OFF w/LLSV OFF= Normal operation if compressor off.
OFF w/LLSV ON=
Compressor operation during startup
time delay if LP delay selected. If
delay is exceeded, turn off Compres-
sor 1, turn on alarm digital output and
send alarm message to S7600. Control
without Compressor 1.
ON w/LLSV OFF =
Compressor on for pump out time de-
lay. If delay is exceeded, turn off Com-
pressor 1, turn on alarm digital output
and send alarm message to S7600.
ON w/LLSV ON =
Normal operation with compressor on.
NOTE: The W7600 must be reset if a Low Pressure
Failure occurs in start-up or normal operation.
Operation as with LP1.
Operation as with LP1.
Operation as with LP1.
INACTIVE =
Normal operation.
ACTIVE = Disable Compressor 1.
INACTIVE =
Normal operation.
ACTIVE = Disable Compressor 2.
INACTIVE =
Normal operation.
ACTIVE = Disable Compressor 3.
INACTIVE =
Normal operation.
ACTIVE = Disable Compressor 4.
INACTIVE =
Economizer enable.
ACTIVE = Economizer disable.
INACTIVE =
Normal operation.
ACTIVE =
Turn on alarm digital output and send mes-
sage to S7600. Does not stop fan if dirty filter
occurs.
NOTE: Not monitored if fan is off.
INACTIVE =
Disable W7600 control.
ACTIVE =
Enable W7600 control.
INACTIVE =
Normal operation.
ACTIVE =
Turn off alarm output; no annunciation.
INACTIVE =
Normal operation.
ACTIVE =
Fan enabled; turn off and lock out heat. Turn
on alarm digital output and send alarm mes-
sage to S7600.
NOTE: The W7600 must be reset if a Heat Failure
occurs.
INACTIVE =
Normal position.
ACTIVE =
Turn on alarm digital output and send alarm
to S7600. Turn off all outputs and disable
control.
NOTE: Not monitored if fan is off.
NOTE: The W7600 must be reset if a Fan Motor
Safety Failure occurs.
20