VAV CONFIGURATION REQUIREMENTS (continued)
Control
Number
Variable Required
To disable heating control, set HEAT_STG =0; otherwise, set HEAT_STG to 1-6 for number of stages.
[CV] HEAT_TYPE
[CV] HEAT_RESET_TYPE
[CV] AUTO_CHANGE
To disable cooling control, set COOL_STG = 0; otherwise, set COOL_STG to 1-12 for number of stages.
[CV] COOL_TYPE
Value
Control
Required
Number
HEATING CONTROL
0, 1, or 2
With 0, 1, or 2
1
196-201 [DO] HEAT1-6
12
13
With 1
212-213 [DO] HEAT+, HEAT-
With 2
54
0, 1, 2, 3, or 4
0 to disable
With 1, 2, 3, or 4
With 1
4
With 2
5
With 3
51
With 4
7
0 or 1
COOLING CONTROL
0, 1, or 2
With 0, 1, or 2
1
27
PM7600B INPUT AND OUTPUT OPTIONS
Dependent
Variable Required
See below.
[CV] TEMP_RATE_LIM
[AI] DA_TMP
[CV] HEAT_STG
[CV] HEAT_TIME
[SP] PRG_DAH_SP or
[AI] DAH_SP
[SP] PRG_DAH_CB or
[AI] DAH_CB
[CV] MOD_HEAT_DELAY
[CV] HEAT_MOTOR_SPEED
[CV] MOD_HEAT_DELAY
[AO] A_HEAT
[CV] HEAT_STG
See below.
None
[SP] HMAX_RESET
[SP] HSTART_RESET
[SP] HEND_RESET
[AI] SP_TMP
[AI] OD_TMP
[AO] A_FAN
[AI] RA_TMP
None
See below.
[CV] TEMP_RATE_LIM
[AI] DA_TMP
[CV] COOL_STG
PM7600B
Dependent
Value Required
1°-20° F/minute
Must be
configured.
1-6
Equal
HEAT_STGs
0-3780 seconds
60° to 130° F
Set
PRG_DAH_SP
to Unprog.,
0° F or -18° C.
1° to 50° F
Set
PRG_DAH_CB
to Unprog. or 0.
0-180 seconds
30-160 seconds
Must be
configured.
0-180 seconds
Must be
configured.
Must equal 1.
N/A
50° to 150° F
0° to 200° F
0° to 200° F
Must be
configured.
N/A
1°-20° F/minute
Must be
configured.
1-12
63-4309—2