Honeywell PM7600B Manual page 23

Network compatible variable air volume program module for w7600
Table of Contents

Advertisement

Point Name
Compressor or Unloader Stage 1 COOL1
Compressor or Unloader Stage 2 COOL2
Compressor or Unloader Stage 3 COOL3
Compressor or Unloader Stage 4 COOL4
Compressor or Unloader Stage 5 COOL5
Compressor or Unloader Stage 6 COOL6
Compressor or Unloader Stage 7 COOL7
Compressor or Unloader Stage 8 COOL8
Compressor or Unloader Stage 9 COOL9
Compressor or Unloader Stage 10 COOL10
Compressor or Unloader Stage 11 COOL11
Compressor or Unloader Stage 12 COOL12
Liquid Line Solenoid Valve 1
Liquid Line Solenoid Valve 2
Liquid Line Solenoid Valve 3
Liquid Line Solenoid Valve 4
Fan Output
Heating Stage 1
Heating Stage 2
Heating Stage 3
Heating Stage 4
Heating Stage 5
Heating Stage 6
Alarm Output
Supply Motor Open
1
(Floating Output)
DIGITAL OUTPUTS
S7600
Control
Label
Number
178
OFF =
ON =
179
OFF =
ON =
180
OFF =
ON =
181
OFF =
ON =
182
OFF =
ON =
183
OFF =
ON =
184
OFF =
ON =
185
OFF =
ON =
186
OFF =
ON =
187
OFF =
ON =
188
OFF =
ON =
189
OFF =
ON =
LLSV1
190
OFF =
ON =
LLSV2
191
OFF =
ON =
LLSV3
192
OFF =
ON =
LLSV4
193
OFF =
ON =
FAN
194
OFF =
ON =
HEAT1
196
OFF =
ON =
HEAT2
197
OFF =
ON =
HEAT3
198
OFF =
ON =
HEAT4
199
OFF =
ON =
HEAT5
200
OFF =
ON =
HEAT6
201
OFF =
ON =
ALARM
202
OFF =
ON =
SUPLY+
203
OFF =
ON =
23
PM7600B INPUT AND OUTPUT OPTIONS
Functional Description
Cooling stage 1 off.
Cooling stage 1 on.
Cooling stage 2 off.
Cooling stage 2 on.
Cooling stage 3 off.
Cooling stage 3 on.
Cooling stage 4 off.
Cooling stage 4 on.
Cooling stage 5 off.
Cooling stage 5 on.
Cooling stage 6 off.
Cooling stage 6 on.
Cooling stage 7 off.
Cooling stage 7 on.
Cooling stage 8 off.
Cooling stage 8 on.
Cooling stage 9 off.
Cooling stage 9 on.
Cooling stage 10 off.
Cooling stage 10 on.
Cooling stage 11 off.
Cooling stage 11 on.
Cooling stage 12 off.
Cooling stage 12 on.
Liquid line solenoid valve (Compressor 1) closed.
Liquid line solenoid valve (Compressor 1) open.
Liquid line solenoid valve (Compressor 2) closed.
Liquid line solenoid valve (Compressor 2) open.
Liquid line solenoid valve (Compressor 3) closed.
Liquid line solenoid valve (Compressor 3) open.
Liquid line solenoid valve (Compressor 4) closed.
Liquid line solenoid valve (Compressor 4) open.
Fan off.
Fan on.
Heating stage 1 off.
Heating stage 1 on.
Heating stage 2 off.
Heating stage 2 on.
Heating stage 3 off.
Heating stage 3 on.
Heating stage 4 off.
Heating stage 4 on.
Heating stage 5 off.
Heating stage 5 on.
Heating stage 6 off.
Heating stage 6 on.
No alarm present or silenced through alarm silence
input on S7600.
Alarm present. Turn on annunciation.
No action.
Drive vanes open to increase air volume.
PM7600B
63-4309—2