RUN SCREEN
PM7600B PROGRAMMING SUMMARY
Run Screen (Normal Operation)
For programming and reviewing data, use the S7600 Keyboard
DA_TMP 70.00F MON 12;45A UNOCC 'ALARM"
Display Module. The S7600 displays English language words
PRESS =3.57 INW S_VEL +35.89 FPM
on a 6" wide screen. These words are arranged in "menues."
By pressing the keys located under the screen, selections
Run Screen (Alarms in History)
can be made front the menues (similar to most computer software).
These selections include reviewing load status and entering
DA_TMP 70.00F MON 12;45A UNOCC 'ALARM"
programs.
PRESS =3.57 INW V_PRES +35.89 FPM
PROGRAM
The 13 keys on the front of the S7600 allow the user to quickly
and easily move through menus, reviewing and modifying
Program Access Menu (Press Program)
programs.
IF ACCESS
IF ACCESS
CODE IS NOT
CODE IS
ENTER NEW ACCESS CODE
*
0 0 0 0
0 0 0 0
more
0 0 0 0
more
PROGRAM: SETPOINT TOD UNITS
*
more
TEMPERATURE PRESSURE RESET VELOCITY *
more
DA COOL SETPOINT CONTROL BAND
*
more
+70F
+2F
DA HEAT SETPOINT CONTROL BAND *
SCH1 OCC UNOCC OCC UNOCC
more
+65F
+4F
more
24 HR UNOCCUPIED
WARMUP
SETPOINT
*
SCH2 OCC UNOCC OCC UNOCC
more
+68F
more
24 HR OCCUPIED
SETBACK SETPOINT
*
more
+60F
ECONOMIZER MIN POS OFFSET IAQ MIN POS *
SCH32 OCC UNOCC OCC UNOCC
more
10%
+8F
3-%
more
11:20 A 11:50A 12:10 P 12:30P
MA PREHEAT SETPT CRTL BAND OA LOCKOUT *
more
+55F
+6F
+5oF
MIXED AIR LIMITS
HIGH
LOW
*
end
+90F +40F
COOL RESET:
SETPOINT START END
more
60F
SUPPLY STATIC PRES SETPT CTRL BAND *
more
+3.5INW
+2.0INW
HEAT RESET:
SETPOINT START END *
end
+100F
RETURN CFM
% OF SUPPLY
CRTL BAND
*
more
80.00%
6.00%
VELOCITY
MINIMUM LIMIT
RETURN STATIC LIMITS
HIGH
LOW
*
more
+180.5FPM
end
+3.0INW
-1.0INW
LO TO HI SPEED FAN: SWITCH HYSTERESIS *
more
+300.0FPM
HI TO LO SPEED FAN:
end
4 keys for SELECTING main functions
PROGRAM
4 keys for MOVING from one menu to another
2 keys for MODIFYING data
+
-
3 keys for PERFORMING special functions
FAST
ENTER ACCESS CODE
0 0 0 0
DISPLAY METRIC (S) UNITS
TOD: SCHEDULES EQUIPMENT HIOLDAYS CLOCK *
end
more
EQU SCH#5 OCC UNOCC OCC UNOCC
more SUN 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more MON 10:20A 11:20A 12:20P 12:50P
32 POSSIBLE
EQU SCH#5 OCC UNOCC OCC UNOCC
SCHEDULES
more TUE 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more WED 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more THU 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
more FRI 10:20A 11:20A 12:20P 12:50P
*
EQU SCH#5 OCC UNOCC OCC UNOCC
+65F
+70F
more SAT 10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
+65F
+70F
more SP1
10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
TIME DELAY
*
more SP2
10:20A 11:20A 12:20P 12:50P
+60.0SEC
EQU SCH#5 OCC UNOCC OCC UNOCC
+60.1FPM
more SP3
10:20A 11:20A 12:20P 12:50P
EQU SCH#5 OCC UNOCC OCC UNOCC
TIME DELAY
*
more SP4
10:20A 11:20A 12:20P 12:50P
+60.0SEC
45
First, select the main function to be performed (PROGRAM,
REVIEW, BYPASS, or RUN) by pressing the desired key. To
REVIEW
BYPASS
RUN
modify data using the PROGRAM mode ot to BYPASS, a
security access code must be entered - no security access is
required for a REVIEW or RUN.
Notice the cursor line under the first line of a word in the
menu. The position of this cursor indicates the user's choice
from the menu.
ALARM
To move the cursor to another choice, press the
CLEAR
SILENCE
To move to the next menu, press the
To move to the previous menu, press the
+
-
To modify data, press
or
When in Program Mode Main Menu, pressing
keys simultaneously will display the HIDDEN SCREEN
Pressure Gains (Hidden/Special)
SUPPLY PRESSURE: p_kd
more
NO
RETURN CFM:
more
Temperature Gains (Hidden/Special)
TEMPERATURE:
PRESS CLEAR TO DELETE A HOLIDAY
more
+1.356 +.7035 +4.762
(IN PROGRAM MODE ONLY)
REHEAT:
t_kp
HOLIDAY START DATE END DATE DAY SCH
more
+.7035
more
MAY 25 1991 MAY 25 1991 SP4
CONFIRM: CLEAR PROGRAMMEMORY?
HOLIDAY2 START DATE END DATE DAY SCH
+ = YES ANY OTHER KEY = NO
more
JULY 4 1991
JULY 4 1991 SP4
24 POSSIBLE
HOLIDAYS
HOLIDAY START DATE
END DATE DAY SCH
more
NOV 23 1991
NOV 25 1991 SP2
DISPLAY CLOCK ON RUN SCREEN
more
YES
SET:
TIME
DATE
FORMAT
more
10:50A
SEP 20 91
12 HR
DAYLIGHT SAVINGS
ENABLE TIME BASE
more
YES
50-60HZ
DAYLIGHT SAVINGS MONTH DOW WEEK
more
START
APR
SUN
1
DAYLIGHT SAVINGS MONTH DOW WEEK
more
END
OCT
SUN
5
PM7600B
PROGRAMMING
or
key.
key.
key.
key.
-
+
and
p_kp
p_ki
+4.356 +.0035 +9.762
p_kp
p_ki
+.0035
+9.762
t_kd
t_kp
t_ki
t_ki
+4.762
M4142A