Trane ADAPTIVE CONTROL UCM-CLD Installation Operation & Maintenance page 12

Operating and control principles
Table of Contents

Advertisement

Default = Disable
Select = Return water
Zone
Outdoor air
[TYPE]
Return water
Default = 50%
Range = 10% to 120%
Zone
Default = 100%
Range = 50% to 300%
Outdoor
Default = 10%
Range = -80% to 80%
[TYPE]
Return:
Default = 2,7°C
Range = 0° to 11°C
Zone
Default = 25°C
Range = 10 to 55°C
Outdoor
Default = 32°C
Range = 10 to 55°C
[TYPE]
Return water
Default = 2,7°C
Range = 0° to 11°C
Zone
Default = -15°C
Range = 0° to 11°C
Outdoor
Default = 2,7°C
Range = 0° to 11°C
Default = Disable
Default = -3°C
Select = -7 to -1°C
Chilled water reset type
"Press (+) (-) to change setting"
Type of chilled water reset selected above
Return water
Zone
Outdoor air
[TYPE] type, reset ratio
"Press (+) (-) to change setting"
[TYPE] type, start reset setpoint
"Press (+) (-) to change setting"
[TYPE] type, max reset setpoint
"Press (+) (-) to change setting"
Ice machine control
"Press (+) (-) to change setting"
Panel ice termination setpoint
"Press (+) (-) to change setting"
12
[TYPE]
Next
Disable
XXX %
Next
XXX C
Next
Next
[Disable/Enable]
XXX F
Next