Control Logic (Sink/Source) Change (Standard Model / Ethernet Model) - Mitsubishi Electric 800 Series Instruction Manual

575v class, compact, high functionality inverters, 0.75k-7.5k
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Safety input/output signal
Termin
Type
al
Terminal name
symbol
24 VDC power supply
common
SD
External transistor
common (source)
Safety input terminal
common
PC
24 VDC power supply Can be used as a 24 VDC 0.1 A power supply.
Safety input (channel
SX1
1)
Safety input (channel
SX2
2)
Safety output
SY1
(channel 1)
Safety output
SY2
(channel 2)
Safety output
SC1
common (channel 1)
Safety output
SC2
common (channel 2)
*1
Refer to the FR-E800-SCE Instruction Manual (Functional Safety).
 Communication
Terminal
Type
symbol
*1
Do not connect the parameter unit. The inverter may be damaged.
*2
USB bus power connection is available. The maximum SCCR is 500 mA.
*3
Refer to the FR-E800 Instruction Manual (Function).
2.6.4
Control logic (sink/source) change (Standard
model / Ethernet model)
The control logic of input signals can be switched as necessary for the standard model and the Ethernet model.
To change the control logic, change the DIP switch position on the control circuit board.
The initial setting of the control logic differs depending on the specification.
50
2. Installation and Wiring
2.6 Control circuit
Common output terminal for 24 VDC 0.1 A power supply
(terminal PC). Isolated from terminal 5.
Common terminal for terminals SX1 and SX2.
Terminal functions can be selected using Pr.S051 SX1/SX2
terminal function selection.
Terminal functions can be selected using Pr.S055 SY1/SY2
terminal function selection.
Common terminal for terminal SY1
Common terminal for terminal SY2
Terminal name
Communication can be made via Ethernet.
Category: 100BASE-TX/10BASE-T
Transmission method: Baseband
Data transmission speed: 100 Mbps (100BASE-TX) / 10 Mbps (10BASE-T)
Ethernet connector (2
Maximum segment length: 100 m between the hub and the inverter
*1
Interface: RJ-45
ports)
Number of cascade connection stages: Up to 2 (100BASE-TX) / up to 4
(10BASE-T)
Number of interfaces available: 2
IP version: IPv4
Mini B connector (receptacle).
By connecting the inverter to a personal computer via this connector, FR
Configurator2 installed on the computer can be used for setting the inverter, or
*2
monitoring or testing the inverter operation.
USB B connector
Interface: conforms to USB 1.1 (USB 2.0 full-speed compatible)
Transmission speed: 12 Mbps
Power supply: 5 V, 100 mA (500 mA maximum)
Terminal function description
Terminal function description
Refer
Rated specification
to page
56
Power supply voltage
*1
range:
22 to 26.5 VDC,
permissible load current:
*1
100 mA
Input resistance: 4.7 kΩ,
*1
voltage when contacts
are open:
21 to 26 VDC,
current when contacts are
*1
short-circuited:
4 to 6 mADC
Permissible load: 24 VDC
*1
(27 VDC at maximum),
0.1 A (The voltage drop is
3.4 V at maximum while
*1
the signal is ON.)
*1
*1
Refer
to page
*3
*3

Advertisement

Table of Contents
loading