Mitsubishi Electric 800 Series Instruction Manual page 64

575v class, compact, high functionality inverters, 0.75k-7.5k
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Wiring method
 Connection
1.
Turn OFF the power of the programmable controller and the inverter.
2.
Remove the inverter front cover.
3.
Check the orientation of the connectors. Insert the connector part of the Ethernet cable to the communication
connector until it clicks.
 Disconnection
1.
Turn OFF the power of the programmable controller and the inverter.
2.
Remove the inverter front cover.
3.
Hold down the latch on the Ethernet cable connector, and pull out the cable while holding the latch.
 Wiring precautions
This section explains Ethernet cable connection and the relevant precautions.
 Handling of the Ethernet cable
• Do not touch the conductors of the cable or the connector on the inverter. Keep the conductors free of dust or dirt. If oil
from your hand, dirt or dust is attached to the core, it can increase transmission loss, arising a problem in data link.
• Check the following:
Is any Ethernet cable disconnected?
Is any of the Ethernet cables shorted?
Are the connectors securely connected?
• Do not use Ethernet cables with broken latches. Doing so may cause the cable to unplug or malfunction.
• The maximum station-to-station distance is 100 m. However, the distance may be shorter depending on the operating
environment of the cable. For details of the cable, contact your cable manufacturer.
 Connecting and disconnecting of the Ethernet cable
Hold the connector part when connecting and disconnecting the Ethernet cable. Pulling a cable connected to the inverter may
damage the inverter or cable, or result in malfunction due to poor contact.
 Network configuration
Check the network configuration before wiring, and perform correct wiring.
 Communication operation
• Using the Ethernet connector as a computer network port enables communication operation from a computer. When the
inverter is connected with a personal, FA or other computer by a communication cable, a user program can run to monitor
the inverter or read and write parameters.
For details, refer to the FR-E800 Instruction Manual (Communication).
2. Installation and Wiring
2.7 Communication connectors and terminals
1
2
3
4
5
6
7
8
9
10
63